Pepperl+Fuchs VAA-2E1A-CB10-SJ/E2J-FL
AS-Interface safety module

Pepperl+Fuchs VAA-2E1A-CB10-SJ/E2J-FL
  • Connection of contact safety switches, e.g. EMERGENCY STOP button
  • Applications up to Cat. 4, PLe / SIL3
  • Modular safety solution
  • Ultra-compact enclosure
Item Number: VAA-2E1A-CB10-SJ/E2J-FL
105.58
-
+
Total price: 105.58
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 2000 Hz, 10 cycles
LED OUTSwitching state (output); LED yellow
Electrical safetyIEC 61140:2009
Degree of protectionIP20 according to EN 60529
Rated insulation voltage32 V
NoteThis device is maintenance-free. If the device is used in a manner not specified by the manufaturer, the protection provided by the device may be impaired.
Number/Type2 safety-related inputs for mechanical contacts, crossed-circuit monitored:
2 single-channel contacts: Up to category 2/PLc in accordance with ISO 13849-1 or SIL 1 in accordance with IEC 62061
1 two-channel contact: Up to category 4/PLe in accordance with ISO 13849-1 or SIL 3 in accordance with IEC 62061
LED INswitching state (input); 2 LED yellow
UL approvalProtection class IP20 is not included in the UL approval. The protection class is tested by Pepperl+Fuchs.
Supplyfrom AS-Interface
ID2 code0
Surge protectionUe: Over voltage category III, safe isolated power supplies (PELV)
AS-Interface specificationV3.0
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
ProfileS-7.B
ID codeB
Data bits (function via AS-Interface) input output
Mass28 g
Protection classIII
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Climatic conditionsFor indoor use only
IO code7
Fieldbus standardEN 62026-2:2013
ID1 codeF
UL File NumberE223772
Rated operating current≤ 40 mA (without inputs/outputs)/max. 160 mA
Degree of protectionEN 60529:2000
LED FAULTerror display; LED red
red: communication error or address is 0
Voltage20 ... 30 V DC pulsed
Rated operating voltage26.5 ... 31.6 V from AS-Interface (PELV)
Pollution degree2
Pulse withstand voltage0.8 kV
Slave typeSafety-Slave
Altitude≤ 5000 m above MSL
Parameter bits (programmable via AS-i)function
Emitted interferenceEN 61000-6-4:2007
Number/Type1 conventional electronic output, PNP , overload and short-circuit resistant
Noise immunityIEC 62026-2:2013 EN 61326-3-1:2017 EN 61000-6-2:2005
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
Relative humidity85 % , noncondensing
Current≤ 100 mA
Supplyfrom AS-Interface
Functional safetyEN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015
Connection200 mm, PVC cable 0.5 mm2
AS-InterfaceEN 62026-2:2013
Voltage(UASI - 7.0 V) ≤ UOUT ≤ UASI
Required master specification≥ V2.1
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Currentinput current limited ≤ 15 mA,
short-circuit protected

Comments

No comments yet

Write a comment