Pepperl+Fuchs VAA-2E2A-G12-SAJ/EA2L
AS-Interface safety module

Pepperl+Fuchs VAA-2E2A-G12-SAJ/EA2L
  • Switchable internal logic operation of the inputs and outputs via parameter bit
  • One-piece housing with stainless steel base
  • Installation without tools
  • Metal threaded inserts with SPEEDCON technology
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Red LED per channel, lights up in the event of output overload
  • Communication monitoring, configurable
  • 2 safe inputs for mechanical contacts such as EMERGENCY-STOP switch
  • DIN rail mounting
  • AS-Interface certificate
Item Number: VAA-2E2A-G12-SAJ/EA2L
216.01
-
+
Total price: 216.01
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
MountingMounting plate
IO code7
Voltage (UAUX - 0.5 V)
Electrical safetyIEC 60947-1, NFPA 79, IEC 60204-1:2007
LED OUTSwitching status (output); 2 yellow/red LEDs
Yellow: output active
Red: output overload
ID codeB
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Insulation coordinationEN 60947-1:2007
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: Output supply overload
Auxiliary voltage (output)24 V DC В± 15 % PELV
Current1.5 A per output , short-circuit protected
AS-Interface specificationV2.1
Noise immunityIEC 62026-2:2008 EN 62061:2005 EN 61000-6-2:2005
Number/Type2 conventional electronic outputs, PNP
Climatic conditionsFor indoor use only
Tightening torque, cable gland0.4 Nm
Voltage20 ... 30 V DC pulsed
StandardsNFPA 79:2007 ER 1
Required master specification V2.1
Protection classIII
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
PFDno significant contribution to PFD of the overall system
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
Supplyfrom AS-Interface
MTTFdno significant contribution to MTTFd of the overall system
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Emitted interferenceEN 61000-6-4:2007/A1:2011
Fieldbus standardEN 62026-2:2013
Performance level (PL)PL e
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Rated insulation voltage40 V
Altitude 2000 m above MSL
Slave typeSafety-Slave
Rated operating current 50 mA
ProfileS-7.B
AS-InterfaceEN 62026-2:2013
Parameter bits (programmable via AS-i)function
CategoryCat. 4
Pollution degree3
ID2 code0
Functional safetyISO 13849-1 (up to category 4/PL e), IEC 61508/IEC 62061 (up to SIL3)
Degree of protectionIP67
Number/Type2 safety-related inputs for mechanical contacts, crossed-circuit monitored:
2 single-channel contacts: up to category 2/PL c to ISO 13849-1 or
1 2-channel contact: up to category 4/PL e to ISO 13849-1
Cable length must not exceed 300 m per input.
Supplyfrom external auxiliary voltage UAUX
Shock and impact resistance30 g, 11 ms in 6 spatial directions 3 shocks
10 g, 16 ms in 6 spatial directions 1000 shocks
Relative humidity85 % , noncondensing
Current loading capacityinput current limited 15 mA,
overload and short-circuit resistant
Mass200 g
Degree of protectionEN 60529:2000
Data bits (function via AS-Interface) input output
Rated operating voltage26.5 ... 31.6 V from AS-Interface
PFHdno significant contribution to PFH of the overall system
ID1 codeF
LED INswitching state (input); 2 LED yellow
Safety Integrity Level (SIL)SIL 3
UL File NumberE223772
Pulse withstand voltage0.5 kV

Comments

No comments yet