Pepperl+Fuchs VAA-2E2A-KE1-S/E2
AS-Interface safety module

Pepperl+Fuchs VAA-2E2A-KE1-S/E2
We ship to United States of America!
  • 2 safe inputs for mechanical contacts such as EMERGENCY-STOP switch
  • Housing with removable terminals
  • Communication monitoring
  • Power supply of outputs from the external auxiliary voltage
  • Power supply of inputs from the module
  • Function display for bus, ext. auxiliary voltage, inputs and outputs
  • Output overload monitoring
  • Switchable internal logic operation of the inputs and outputs via parameter bit
  • Addressing jack
Item Number: VAA-2E2A-KE1-S/E2
186.34
-
+
Total price: 186.34
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Relative humidity85 % , noncondensing
Ambient temperature-25 ... 50 В°C (-13 ... 122 В°F)
LED OUTSwitching state (output); 2 LED yellow
Safety Integrity Level (SIL)SIL 3
Parameter bits (programmable via AS-i)function
LED INswitching state (input); 2 LED yellow
Supplyfrom external auxiliary voltage UAUX
Slave typeSafety-Slave
AS-InterfaceEN 62026-2:2013
ID codeB
MountingDIN mounting rail
Emitted interferenceEN 61000-6-4:2001
AS-Interface specificationV2.1
LED AUXext. auxiliary voltage UAUX ; LED green
StandardsNFPA 79:2002
Electrical safetyEN 50178:1998 IEC 60204-1:2007
LED PWRAS-Interface voltage; LED green
Rated operating voltage26.5 ... 31.6 V from AS-Interface
ID2 code0
Supplyfrom AS-Interface
Climatic conditionsFor indoor use only
Connectionremovable terminals, terminal connection 2.5 mm2
Auxiliary voltage (output)20 ... 30 V DC PELV
Performance level (PL)PL e
Degree of protectionEN 60529:2000
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-4-5:2005 1 kV asymmetric, criterion B, EN 61000-6-4:2007
Pollution degree2
MTTFd200 a
Required master specification V2.1
Current loading capacityinput current limited 15 mA,
overload and short-circuit resistant
Voltage (UAUX - 0.5 V)
Current0.5 A per output
Shock and impact resistance10 g, 16 ms in 6 spatial directions 1000 shocks
PFD0
Voltage20 ... 30 V DC pulsed
Number/Type2 safety-related inputs for mechanical contacts, cross-circuit monitored:
2 single-channel contacts: up to category 2 in accordance with EN 954-1 or
1, 2-channel contact: up to category 4 in accordance with EN 954-1
Cable length must not exceed 300 m per input.
UL File NumberE223772
Rated operating current 70 mA
PFHd0
ID1 codeF
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Data bits (function via AS-Interface) input output
IO code7
Insulation coordinationEN 50178:1998
ProfileS-7.B
Number/Type2 conventional electronic outputs, PNP
Altitude 2000 m above MSL
Degree of protectionIP20
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Mass80 g
Fieldbus standardEN 62026-2:2013
Tightening torque of clamping screws0.5 Nm ... 0.6 Nm
Protection classIII
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: Output supply overload
Functional safetyEN ISO 13849-1:2006 up to PL e, IEC 61508:2009 up to SIL 3

Buy Pepperl+Fuchs VAA-2E2A-KE1-S/E2 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is a world-known industrial automation supplier. In our catalog, you can find over 3 million products. We provide delivery worldwide cooperating with the best logistics companies. We offer you highly competitive prices for all items from our catalog. We give our customers delayed payments and better conditions when long-term cooperation. We are a stable and reliable company which has earned the trust of many customers, as can be seen from our client list.

Comments

No comments yet

Write a comment