Pepperl+Fuchs VAA-2E2A-KE1P-S/E2
AS-Interface safety module
We ship to United States of America!
- 2 safe inputs for mechanical contacts such as EMERGENCY-STOP switch
- Housing with removable terminals
- Communication monitoring
- Power supply of outputs from the external auxiliary voltage
- Power supply of inputs from the module
- Function display for bus, ext. auxiliary voltage, inputs and outputs
- Output overload monitoring
- Switchable internal logic operation of the inputs and outputs via parameter bit
- Addressing jack
Item Number:
VAA-2E2A-KE1P-S/E2
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
Data bits (function via AS-Interface) | |
Tightening torque of clamping screws | 0.5 Nm ... 0.6 Nm |
Insulation coordination | EN 50178:1998 |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
PFD | 0 |
LED AUX | ext. auxiliary voltage UAUX ; LED green |
Mounting | DIN mounting rail |
Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-4-5:2005 1 kV asymmetric, criterion B, EN 61000-6-4:2007 |
Current loading capacity | input current limited ≤ 15 mA, overload and short-circuit resistant |
Voltage | ≥ (UAUX - 0.5 V) |
ID1 code | F |
Supply | from AS-Interface |
Required master specification | ≥ V2.1 |
Altitude | ≤ 2000 m above MSL |
Current | 0.5 A per output |
LED IN | switching state (input); 2 LED yellow |
Voltage | 20 ... 30 V DC pulsed |
AS-Interface | EN 62026-2:2013 |
Climatic conditions | For indoor use only |
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Shock and impact resistance | 10 g, 16 ms in 6 spatial directions 1000 shocks |
Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) |
Pollution degree | 2 |
Electrical safety | EN 50178:1998 IEC 60204-1:2007 |
IO code | 7 |
Performance level (PL) | PL e |
PFHd | 0 |
ID code | B |
LED OUT | Switching state (output); 2 LED yellow |
Mass | 80 g |
Degree of protection | IP20 |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: Output supply overload |
Number/Type | 2 conventional electronic outputs, PNP |
UL File Number | E223772 |
Number/Type | 2 safety-related inputs for mechanical contacts, crossed-circuit monitored: 2 single-channel contacts: up to category 2/PL c to ISO 13849-1 or 1 2-channel contact: up to category 4/PL e to ISO 13849-1 Cable length must not exceed 300 m per input. |
Relative humidity | 85 % , noncondensing |
ID2 code | 0 |
Emitted interference | EN 61000-6-4:2007 |
Connection | removable spring terminals Conductor cross-section 0,25 ... 2,5 mm2 |
Parameter bits (programmable via AS-i) | function |
Slave type | Safety-Slave |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Profile | S-7.B |
Supply | from external auxiliary voltage UAUX |
Degree of protection | EN 60529:2000 |
Fieldbus standard | EN 62026-2:2013 |
Safety Integrity Level (SIL) | SIL 3 |
AS-Interface specification | V2.1 |
Ambient temperature | -25 ... 50 В°C (-13 ... 122 В°F) |
MTTFd | 200 a |
Rated operating current | ≤ 70 mA |
Functional safety | EN ISO 13849-1:2015 up to PL e, IEC 61508:2010 and IEC 62061:2005/A2:2015 up to SIL 3 |
LED PWR | AS-Interface voltage; LED green |
Protection class | III |
Standards | NFPA 79:2002 |
Buy Pepperl+Fuchs VAA-2E2A-KE1P-S/E2 with the best possible price and delivery terms on eltra-trade.com