Pepperl+Fuchs VAA-4E-G2-ZA
AS-Interface sensor module
- AS-Interface certificate
- Degree of protection IP67
- Addressing jack
- Flat cable connection with cable piercing technique, variable flat cable guide
- Inputs for 2- and 3-wire sensors
- Power supply of inputs from the module
- Function display for bus and inputs
- Monitoring of sensor overloads
Item Number:
VAA-4E-G2-ZA
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Input | EN 61131-2:2007 |
AS-Interface | EN 62026-2:2013 |
ID1 code | F |
ID2 code | F |
Mounting | Mounting plate |
Tightening torque, cable gland | 0.4 Nm |
Emitted interference | EN 61000-6-4:2001 |
Current loading capacity | 200 mA (TB 40 В°C), 150 mA (TB 60 В°C), short-circuit protected |
Climatic conditions | For indoor use only |
Parameter bits (programmable via AS-i) | function |
Noise immunity | EN 61000-6-2:2001 |
Degree of protection | IP67 |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
IO code | 0 |
Ambient temperature | -25 ... 60 В°C (-13 ... 140 В°F) |
Input current | 8 mA (limited internally) |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Supply | from AS-Interface |
Altitude | 2000 m above MSL |
Data bits (function via AS-Interface) | |
Relative humidity | 85 % , noncondensing |
Protection class | III |
Profile | S-0.1 |
Slave type | Standard slave |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor supply |
Required master specification | V2.0 |
Connection | cable piercing method flat cable yellow inputs: M12 round connector |
AS-Interface specification | V3.0 |
Pollution degree | 3 |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) |
Fieldbus standard | EN 62026-2:2013 |
LED PWR | AS-Interface voltage; LED green |
Rated operating current | 40 mA (without sensors) / max. 240 mA |
Degree of protection | EN 60529:2000 |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Signal delay | < 2 ms (input/AS-Interface) |
ID code | 1 |
LED IN | switching state (input); 4 LED yellow |
UL File Number | E223772 |
Mass | 100 g |
Voltage | 21 ... 31 V |
Signal frequency | 250 Hz |
People also buy
Comments
No comments yet