Pepperl+Fuchs VAA-4E-G4-ZE
AS-Interface sensor module
- Degree of protection IP67
- Flat or round cable connection (via standardized EMS base, not included with delivery)
- Cable piercing method for flat cable
- Inputs for 2- and 3-wire sensors
- Power supply of inputs from the module
- Function display for bus and inputs
- LED indicator for overload on sensor supply
Item Number:
VAA-4E-G4-ZE
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Data bits (function via AS-Interface) | |
IO code | 0 |
AS-Interface | EN 62026-2:2013 |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Climatic conditions | For indoor use only |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) |
ID code | 0 |
ID2 code | E |
Degree of protection | IP67 |
Input | EN 61131-2:2007 |
Input current | 8 mA (limited internally) |
AS-Interface specification | V3.0 |
Rated operating current | 40 mA (without sensors) / max. 190 mA |
Emitted interference | EN 61000-6-4:2007 |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
ID1 code | F |
Slave type | Standard slave |
Tightening torque, housing screws | 0.8 Nm |
Parameter bits (programmable via AS-i) | function |
Fieldbus standard | EN 62026-2:2013 |
Mounting | DIN rail or screw mounting |
Required master specification | V2.0 |
Degree of protection | EN 60529:2000 |
Pollution degree | 3 |
Current loading capacity | 150 mA (TB 40 В°C), 120 mA (TB 60 В°C), short-circuit protected |
Noise immunity | EN 61000-6-2:2005 |
Relative humidity | 85 % , noncondensing |
Mass | 180 g |
Supply | from AS-Interface |
LED IN | switching state (input); 4 LED yellow |
Ambient temperature | -25 ... 60 В°C (-13 ... 140 В°F) |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Switching point | according to DIN EN 61131-2 (Type 2) |
UL File Number | E223772 |
Connection | cable piercing method or terminal compartment yellow flat cable or standard round cable inputs: M12 x 1.5 cable gland and cage tension spring terminals |
LED PWR/FAULT | dual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply |
Voltage | 21 ... 31 V |
Profile | S-0.0 |
Altitude | 2000 m above MSL |
Protection class | III |
People also buy
Comments
No comments yet