Pepperl+Fuchs VAA-4E4A-G12-ZAJ/EA2L
AS-Interface sensor/actuator module

Pepperl+Fuchs VAA-4E4A-G12-ZAJ/EA2L
  • One-piece housing with stainless steel base
  • Installation without tools
  • Metal threaded inserts with SPEEDCON technology
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Red LED per channel, lights up in the event of output overload
  • Communication monitoring, configurable
  • Inputs for 2-, 3-, and 4-wire sensors
  • DIN rail mounting
  • AS-Interface certificate
Item Number: VAA-4E4A-G12-ZAJ/EA2L
199.72
-
+
Total price: 199.72
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
Pollution degree3
Diagnostic Coverage (DC)0 %
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or outputs
IO code7
Voltage (UAUX - 0.5 V)
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Switching pointaccording to DIN EN 61131-2 (Type 2)
MTTFd190 a
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Voltage21 ... 31 V
UL File NumberE223772
Required master specification V2.1
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
Vibration resistance0.75 mm 10 ... 57 Hz , 5g 57 ... 50 Hz
Relative humidity85 % , noncondensing
ID1 codeF
Degree of protectionEN 60529:2000
Supplyfrom AS-Interface
Mission Time (TM)20 a
Rated operating current 40 mA (without sensors) / max. 240 mA
ID2 codeE
Mass230 g
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Emitted interferenceEN 61000-6-4:2007
ID codeF
Slave typeStandard slave
Current2 A per output
6 A total (TB 40 В°C)
4 A total (TB 70 В°C)
Input current 8 mA (limited internally)
Parameter bits (programmable via AS-i)function
Fieldbus standardEN 62026-2:2013
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Shock and impact resistance30 g, 11 ms in 6 spatial directions 3 shocks
10 g, 16 ms in 6 spatial directions 1000 shocks
Signal delay< 1 ms (input/AS-Interface)
Tightening torque, cable gland0.4 Nm
Data bits (function via AS-Interface) input output
Degree of protectionIP67
AS-InterfaceEN 62026-2:2013
Supplyfrom external auxiliary voltage UAUX
Protection classIII
Current loading capacity 200 mA, overload and short-circuit protected
InputEN 61131-2
AS-Interface specificationV3.0
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
option 2 inputs for 4-wire sensors (PNP), DC
Climatic conditionsFor indoor use only
Auxiliary voltage (output)24 V DC В± 15 % PELV
ProfileS-7.F
LED INswitching state (input); 4 LED yellow
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
LED OUTSwitching status (output); 4 yellow/red LEDs
Yellow: output active
Red: output overload
MountingMounting plate
Altitude 2000 m above MSL
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)

Comments