Pepperl+Fuchs VAA-4E4A-G16-ZEJ/E2L
AS-Interface sensor/actuator module
- Compact design
- Connections via round connector
- AS-Interface connection via M12 metal threaded insert with SPEEDCON
- Function display for bus, ext. auxiliary voltage, inputs and outputs
- Degree of protection IP67 / IP68 / IP69K
- Inputs for 2- and 3-wire sensors
- Supply for inputs from AS-Interface
- Power supply of outputs from the external auxiliary voltage
- Communication monitoring
- Detection of overload on sensor supply
- Detection of output overload with LED per channel
Item Number:
VAA-4E4A-G16-ZEJ/E2L
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Voltage | (UAUX - 0.5 V) |
Mass | 150 g |
Connection | AS-Interface and auxiliary voltage: M12 x 1 round connector sensors/actuators: M8 x 1 round connector |
Altitude | 2000 m above MSL |
LED OUT | Switching status (output); 4 yellow/red LEDs Yellow: output active Red: output overload |
MTTFd | 190 a |
Switching point | according to DIN EN 61131-2 (Type 2) |
UL File Number | E223772 |
LED IN | switching state (input); 4 LED yellow |
ID code | 0 |
Tightening torque, cable gland | 0.4 Nm (M12 connector), 0.2 Nm (M8 connector) |
Current | 1 A per output |
Input | EN 61131-2 |
Rated operating current | 40 mA (without sensors) / max. 240 mA |
AS-Interface specification | V3.0 |
Climatic conditions | For indoor use only |
Data bits (function via AS-Interface) | |
Degree of protection | EN 60529:2000 |
ID2 code | E |
Signal delay | < 1 ms (input/AS-Interface) |
Current loading capacity | 200 mA (TB 40 В°C), 150 mA (TB 70 В°C), overload-proof and short-circuit protected |
Fieldbus standard | EN 62026-2:2013 |
Pollution degree | 3 |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
LED PWR/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply or output overload |
Mission Time (TM) | 20 a |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
Supply | from external auxiliary voltage UAUX |
IO code | 7 |
Noise immunity | EN 61000-6-2:2005 EN 62026-2:2013 |
Diagnostic Coverage (DC) | 0 % |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
Parameter bits (programmable via AS-i) | function |
Emitted interference | EN 61000-6-4:2007 |
Input current | 9 mA (limited internally) |
AS-Interface | EN 62026-2:2013 |
Relative humidity | 85 % , noncondensing |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
Degree of protection | IP67 / IP68 / IP69k |
Protection class | III |
Slave type | Standard slave |
Usage category | DC-13 |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Mounting | screw mounting |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Profile | S-7.0 |
Required master specification | V2.1 |
Ambient temperature | -25 ... 70 В°C (-13 ... 158 В°F) |
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
ID1 code | F |
Supply | from AS-Interface |
Voltage | 21 ... 31 V |
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |