Pepperl+Fuchs VAN-115/230AC-K16
AS-Interface power supply
- AS-Interface certificate
- PELV/SELV
- LED operating display
- 8 A output load
- 115 V AC / 230 V AC switchable
- AS-Interface data decoupling
- Overload protection using FUSE mode
Item Number:
VAN-115/230AC-K16
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Degree of protectionIP20 according to EN 60529
Capacity factor | > 0.5 |
Residual ripple | 50 mVss (500 kHz bandwidth, 50-andOmega;-measurement with ohmic load) |
Ambient temperature | -10 ... 70 В°C (14 ... 158 В°F) (Measured 25 mm below the device) from 60В° C 6W/В°C power recovery necessary |
Efficiency | typ. 92 % (at 230 V AC/8 A) |
Current limit | > 8.4 A |
LED IR on | red LED: ON: Plug-in jumper position 2-3 OFF: Plug-in jumper position 1-2 |
UL File Number | E223176 |
LED AS-i ok | operating display; LED green |
Mass | approx. 890 g |
Voltage | 30.55 V DC В± 3 % |
Short-circuit current | 12 ... 25 A (max. 5 s) |
Electromagnetic compatibility | emitted interference in accordance with EN 50081-2 class B (EN 55011, EN 55022) noise immunity in accordance with EN 61000-6-2, EN 61000-4-2 to EN 61000-4-6, EN 61000-4-11 |
Reset push-button switch | FUSE mode reset |
Connection | Connection terminals, max. conductor cross-section flexible: 0.5 ... 4 mm2 fixed: 0.5 ... 6 mm2 stripped length 7 mm, connector sleeves are permissible |
Pollution degree | 2 |
Galvanic isolation | overvoltage category III |
Rated operating current | 6,0 A (Switch position 115 V) 2.8 A (Switch position 230 V) |
Fusing | T8A/250 V AC HBC (not accessible) |
Short-circuit protection/overload | FUSE Mode (2 ... 5 s current, then trips) |
Current | 8 A |
Plug-in jumper | Position 1-2: Communication Mode Position 2-3: IR addressing |
LED Overload | red LED, flashes in the FUSE mode |
Power selection switch | changeover switch for 115 V AC/230 V AC |
Protection class | 1 (IEC 60536); Protective conductor connection necessary |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Surge protection | limited to max. 55 V |
Rated operating voltage | nominal: 100 ... 120 V AC/220 ... 240 V AC (front end selectable) permissible: 85 ... 132 V AC/184 ... 264 V AC/230 ... 375 V DC |
Supply frequency | 47 ... 63 Hz or DC |
People also buy
Comments
No comments yet