Pepperl+Fuchs VAS-2A-K12-S1
AS-Interface Safety Monitor
We ship to United States of America!
- Two dependent or independent open circuits
- Fulfills technical safety requirements for Category 4 according to EN 954-1, EN 61508, SIL 3 and Performance Level e (PLe)
- Logic configuration by means of drag drop with diagrammatical display on the PC
- Extended logic functions
Item Number:
VAS-2A-K12-S1
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
LED AS-i | from: normal operation red, continuous illuminated: communication error |
Mounting | DIN rail mounting |
LED red | Off: contacts of the safety output (OSSD) closed constantly lit: contacts of the safety output (OSSD) open flashing: error |
Interface type | RS 232, serial |
Degree of protection | EN 60529:2000 |
Surge protection | overvoltage category III for rated operating voltage 300 V DC acc. to VDE 0110 Part 1 |
Mass | 450 g |
Electrical safety | EN 50178:1998 |
LED yellow | off: - constantly lit: startup/restart lock active flashing: external test required |
Rated operating voltage | 24 V DC ?± 15 % Residual ripple 15 % 26.5 ... 31.6 V from AS-Interface |
Transfer rate | 9600 baud, no parity, 1 start bit, 1 stop bit, 8 data bits |
LED POWER | from: no power supply green, continuous illuminated: AS-Interface power supply available |
Safety Integrity Level (SIL) | SIL 3 |
Storage temperature | -30 ... 70 ?°C (-22 ... 158 ?°F) |
AS-Interface | EN 62026-2:2013 |
Degree of protection | IP20 (only for use in electrical operating rooms / switch cabinet suitable with minimum protection type IP54) |
LED green | Off: contacts of the safety output (OSSD) open constantly lit: contacts of the safety output (OSSD) closed flashing: delay time running for Stop Category 1 |
Switch-on delay | < 10 s |
MTTFd | 389 a |
Performance level (PL) | PL e |
Connection | screw terminals |
Rated operating current | 200 mA 45 mA from AS-Interface |
Standards | NFPA 79:2002 |
B10d | 2 E+5 |
AS-Interface specification | V2.1 |
Functional safety | ISO 13849-1:2008 (up to category 4/PL e), IEC 61508:2000/IEC 62061:2005 (up to SIL3) |
Safety output | 2 x 2 potential-free NO contacts, max. contact loading: 1 A DC-13 at 24 V DC, 3 A AC-15 at 230 V AC |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Output type | Signal output: PNP transistor output, 200 mA, short-circuit and reverse-polarity-proof |
Response delay | < 50 ms |
Number/Type | 2 opto-coupling inputs (high-active) ""Start"" and ""protection control (EDM)"", input currents about 10 mA at 24 V DC |
Buy Pepperl+Fuchs VAS-2A-K12-S1 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. provides complete industrial automation solutions. With a wide selection of products and efficient delivery options, we meet your needs effectively. Our focus on quality and customer satisfaction distinguishes us. Experience our exceptional service and support for your automation needs.