Pepperl+Fuchs VAS/M-2A8L-KE4-8SE-C1
AS-Interface Safety Monitor

Pepperl+Fuchs VAS/M-2A8L-KE4-8SE-C1
  • Compact safety controller up to SIL 3/PLe
  • 4 integrated, safe inputs
  • 2 integrated, safe outputs (OSSDs)
  • 8 logical, safe output groups (switchable)
  • Increased functionality through integrated expansion port
  • Parameterizable muting, timer and logic functions using SIMON+ software
  • Integrated data decoupling
Item Number: VAS/M-2A8L-KE4-8SE-C1
1046.47
-
+
Total price: 1046.47
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Mission Time (TM)20 a
Interface typeChip card slot
Number/Type8 / 4 safe inputs cat. 4
or
8 standard inputs and outputs
ID1 codeF
MountingDIN mounting rail
LED O1, O2Status of outlputs, multicolored LED
yellow: Output on
Rated operating current 200 mA from AS-Interface;
4 A from AUX
Degree of protectionIP20
Auxiliary voltage (input)20 ... 30 VDC PELV
Safety Integrity Level (SIL)SIL 3
ID codeB
Input currentStatic switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 andmu;s)
Number/TypeOutput circuits 1 and 2
max. contact rating:
700 m ADC-13 at 24 V
UL File NumberE223772
AS-Interface specificationV3.0
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
PFHd5.08 E-9
Supply24 V UAUX
Current loading capacity10 mA per signal output
1.4 A OSSD supply output
AS-InterfaceEN 62026-2:2013
Interface typeMicro USB
Electrical safetyIEC 61508:2010 and EN 62061:2005 (up to SIL3) EN 13849-1:2008/AC:2009 EN 61326-3-1:2008
LED SMStatus of safety monitor, multicolored LED
green: Safety monitor OK
Electromagnetic compatibilityEN 50295:1999 EN 61000-6-2:2005/AC:2005
EN 61000-6-4:2007/A1:2011
Supply24 V UAUX
LED S1 ... S8Status of inputs S1 ... S8, yellow LED
yellow: Contact open
Ambient temperature0 ... 55 В°C (32 ... 131 В°F)
ProfileS-0.B.E
LED AS-i MStatus of AS interface master, multicolored LED
green: Master OK
Insulation voltage500 V AS-Interface/UAUX:
Rated operating voltage18,0 ... 31.6 V from AS-Interface
Degree of protectionEN 60529:2000
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Performance level (PL)PL e
IO code0