Pepperl+Fuchs VBA-2A-G11-I-V1
AS-Interface analog module
- Degree of protection IP68 / IP69K
- Function display for bus and outputs
- Accuracy В± 0.15 %
- Integrated shielding
- Channel-specific output monitoring
- Communication monitoring
Item Number:
VBA-2A-G11-I-V1
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Climatic conditions | For indoor use only |
Tightening torque, housing screws | 1.8 Nm |
Degree of protection | IP68 / IP69K |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, IEC 62026-2:2008 |
Protection class | III |
Supply | from AS-Interface |
Emitted interference | EN 61000-6-4:2007 |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) |
Profile | S-7.3.5 |
Connection | AS-Interface: M12 round connector Outputs: M12 round connector |
ID code | 3 |
AS-Interface | EN 62026-2:2013 |
Diagnostic Coverage (DC) | 0 % |
Relative humidity | 85 % , noncondensing |
Required master specification | V2.1 |
ID2 code | 5 |
Fieldbus standard | EN 62026-2:2013 |
MTTFd | 370 a |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
Degree of protection | EN 60529:2000 |
Load | max. 600 andOmega; |
Pollution degree | 3 |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Mass | 200 g |
Ambient temperature | -25 ... 70 В°C (-13 ... 158 В°F) |
ID1 code | F |
Mission Time (TM) | 20 a |
UL File Number | E223772 |
Altitude | 2000 m above MSL |
LED ANALOG | Status of output signal; yellow LED Yellow: 0 mA I 23 mA Yellow flashing: lead breakage or I > 23 mA |
Number/Type | 2 analog outputs (current), 0 ... 20 mA |
Rated operating current | 100 mA |
IO code | 7 |
Accuracy | 0.15 % of full-scale value |
Tightening torque, cable gland | 0.4 Nm |
Parameter bits (programmable via AS-i) | function |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
Resolution | 6 andmicro;A |
Temperature influence | 1 andmicro;A/K |
AS-Interface specification | V3.0 |
Mounting | Mounting plate |
Slave type | Standard slave |
People also buy