Pepperl+Fuchs VBA-2A-KE5-IL/UL
AS-Interface analog module

Pepperl+Fuchs VBA-2A-KE5-IL/UL
  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Power supply of outputs from the external auxiliary voltage
  • Function display for bus, external auxiliary voltage and outputs
Item Number: VBA-2A-KE5-IL/UL
241.49
-
+
Total price: 241.49
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Temperature influence1 andmicro;A/K or 0,3 mV/K
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
LED OUTStatus of output signal; yellow LED
Yellow: output value within value range
Continually on: current mode
1.4 s on/0.1 s off: voltage mode
Flashing yellow: wire break (at current output) or output value outside of value range
Altitude 2000 m above MSL
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Short-circuit currentvoltage output: max. 22 mA
AS-Interface specificationV3.0
Protection classIII
Relative humidity85 % , noncondensing
Parameter bits (programmable via AS-i)function
ID1 codeF
Auxiliary voltage (output)24 V DC В± 15 % PELV
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Current consumptionIAUX 650 mA
Loadvoltage output: min. 1 kandOmega;
current output: max. 600 andOmega;
ResolutionVoltage output: 3 mV
Current output: 6 andmicro;A
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Number/TypeTwo analog outputs
Current: 0 mA ... 20 mA
Voltage: 0 V ... 10 V
Pollution degree2
AS-InterfaceEN 62026-2:2013
LED FAULTFault indication: red LED
Red: communication error or address is 0
Red flashing: peripheral fault
Degree of protectionIP20
Slave typeStandard slave
MTBF197 a
Emitted interferenceEN 61000-6-4:2007
UL File NumberE223772
ProfileS-7.3.5
ConnectionRemovable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Current loading capacity 600 mA (signal current + actuator power supply) from external auxiliary voltage UAUX, overload-proof and short-circuit proof
Mass110 g
Required master specification V2.1
Rated operating current 75 mA
SupplyFrom auxiliary voltage UAUX
Climatic conditionsFor indoor use only
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
LED PWRAS-Interface voltage; green LED
Green: voltage OK
Flashing green: address 0 or peripheral error
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Fieldbus standardEN 62026-2:2013
IO code7
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
ID2 code5
ID code3
NoteMax. length of jumpers = 5 cm
MountingDIN mounting rail
Degree of protectionEN 60529:2000
Accuracy0.15 % of full-scale value

Comments