Pepperl+Fuchs VBA-2E-G11-I/U/PT100-V1
AS-Interface analog module
- Function display for bus, internal and external sensor power supply, inputs
- Supply for inputs from AS-Interface or auxiliary voltage
- Degree of protection IP68 / IP69K
- Accuracy В± 0.1 %
- Channel-specific input monitoring
- Inputs for current, voltage or Pt100 temperature sensor
- Overview
- Comments
IO code | 7 |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
ID code | 3 |
Connection | AS-Interface/UAUX: M12 round connector Inputs: M12 round connector |
Degree of protection | EN 60529:2000 |
Mission Time (TM) | 20 a |
Tightening torque, housing screws | 1.8 Nm |
ID1 code | F |
Required master specification | V2.1 |
Protection class | III |
AS-Interface specification | V3.0 |
Fieldbus standard | EN 62026-2:2013 |
Pollution degree | 3 |
Rated operating current | 60 mA (without sensors) / max. 200 mA |
Supply | from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT) |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
Measuring current | for Pt100: approx. 1 mA |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Parameter bits (programmable via AS-i) | function |
Mass | 200 g |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
Climatic conditions | For indoor use only |
UL File Number | E223772 |
LED ANALOG | status of input signal; LED yellow off: not active on: signal within measurement range flashing: signal outside of measurement range |
Tightening torque, cable gland | 0.4 Nm |
Temperature influence | Voltage/current: 20 ppm/K Pt100: (10 ppm of indicated temperature [В°C] + 0.003 В°C)/K |
Current loading capacity | 140 mA from AS-Interface; overload and short-circuit resistant 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected |
Number/Type | 2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V Pt100: -200 ... 850 В°C |
MTTFd | 190 a |
Altitude | 2000 m above MSL |
Relative humidity | 85 % , noncondensing |
Accuracy | Voltage/current: 0.1% of accumulated value Pt100: 0.1% of indicated temperature [В°C] + 0.3 В°C |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
LED INT/EXT | status display input supply; LED green green: input supply from AS-Interface off: input supply from auxiliary voltage |
Slave type | Standard slave |
Resolution | 16 Bit / 1 andmicro;A (current input) or 16 bit / 1 mV (voltage input) or 16 Bit / 0.1В°C (temperature input) |
Input resistance | current input: max. 70 andOmega; voltage input: 100 kandOmega; |
Degree of protection | IP68 / IP69K |
Profile | S-7.3.D |
Ambient temperature | -25 ... 70 В°C (-13 ... 158 В°F) |
Emitted interference | EN 61000-6-4:2007 |
AS-Interface | EN 62026-2:2013 |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
Input | EN 61131-2:2007 |
Diagnostic Coverage (DC) | 0 % |
Mounting | Mounting plate |
ID2 code | D |
People also buy
Comments
No comments yet