Pepperl+Fuchs VBA-2E-G11-I/U/PT100-V1
AS-Interface analog module

Pepperl+Fuchs VBA-2E-G11-I/U/PT100-V1
We ship to United States of America!
  • Function display for bus, internal and external sensor power supply, inputs
  • Supply for inputs from AS-Interface or auxiliary voltage
  • Degree of protection IP68 / IP69K
  • Accuracy В± 0.1 %
  • Channel-specific input monitoring
  • Inputs for current, voltage or Pt100 temperature sensor
Item Number: VBA-2E-G11-I/U/PT100-V1
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
IO code7
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
ID code3
ConnectionAS-Interface/UAUX: M12 round connector
Inputs: M12 round connector
Degree of protectionEN 60529:2000
Mission Time (TM)20 a
Tightening torque, housing screws1.8 Nm
ID1 codeF
Required master specification V2.1
Protection classIII
AS-Interface specificationV3.0
Fieldbus standardEN 62026-2:2013
Pollution degree3
Rated operating current 60 mA (without sensors) / max. 200 mA
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT)
Auxiliary voltage (output)20 ... 30 V DC PELV
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: peripheral fault
Measuring currentfor Pt100: approx. 1 mA
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Parameter bits (programmable via AS-i)function
Mass200 g
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Climatic conditionsFor indoor use only
UL File NumberE223772
LED ANALOGstatus of input signal; LED yellow
off: not active
on: signal within measurement range
flashing: signal outside of measurement range
Tightening torque, cable gland0.4 Nm
Temperature influenceVoltage/current: 20 ppm/K
Pt100: (10 ppm of indicated temperature [В°C] + 0.003 В°C)/K
Current loading capacity 140 mA from AS-Interface; overload and short-circuit resistant
600 mA from external auxiliary voltage UAUX , overload and short-circuit protected
Number/Type2 analog inputs
Current: 0 ... 20 mA/4 ... 20 mA
voltage: 0 ... 10 V
Pt100: -200 ... 850 В°C
MTTFd190 a
Altitude 2000 m above MSL
Relative humidity85 % , noncondensing
AccuracyVoltage/current: 0.1% of accumulated value
Pt100: 0.1% of indicated temperature [В°C] + 0.3 В°C
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INT/EXTstatus display input supply; LED green
green: input supply from AS-Interface
off: input supply from auxiliary voltage
Slave typeStandard slave
Resolution16 Bit / 1 andmicro;A (current input) or
16 bit / 1 mV (voltage input) or
16 Bit / 0.1В°C (temperature input)
Input resistancecurrent input: max. 70 andOmega;
voltage input: 100 kandOmega;
Degree of protectionIP68 / IP69K
ProfileS-7.3.D
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
InputEN 61131-2:2007
Diagnostic Coverage (DC)0 %
MountingMounting plate
ID2 codeD

Buy Pepperl+Fuchs VBA-2E-G11-I/U/PT100-V1 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is an electrical wholesaler online. We offer an enhanced product range of automation products. We can ship your order on the same day. We offer our clients only cost-effective solutions. The main advantage is that we always have a solution for you. Our company has a stable image of one of the best in our field, and we constantly prove it.