  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Sensors can be supplied either from the AS-Interface or external auxiliary voltage, as preferred
  • Function indicator for the bus, external auxiliary voltage, internal sensor supply, and inputs
Item Number: VBA-2E-KE5-IJL/UJL
250.78
-
+
Total price: 250.78
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Relative humidity85 % , noncondensing
Resolution15 Bit
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Altitude 2000 m above MSL
LED PWRAS-Interface voltage; green LED
Green: voltage OK
Flashing green: address 0 or peripheral error
Fieldbus standardEN 62026-2:2013
Input resistancecurrent input: max. 70 andOmega;
voltage input: 100 kandOmega;
UL File NumberE223772
MTBF154 a
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
ProfileS-7.3.D
Number/Type2 analog inputs
Current: 0 ... 20 mA/4 ... 20 mA
voltage: 0 ... 10 V
Degree of protectionIP20
NoteMax. length of jumpers = 5 cm
Emitted interferenceEN 61000-6-4:2007
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Slave typeStandard slave
SupplyFrom AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX)
Temperature influence1 andmicro;A/K or 0,3 mV/K
Parameter bits (programmable via AS-i)function
LED INTInternal input supply active; LED green
LED INstatus of input signal; LED yellow
off: not active
on: signal within measurement range
flashing: signal outside of measurement range
MountingDIN mounting rail
IO code7
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Protection classIII
Required master specification V2.1
Current consumptionIAUX 650 mA
ID2 codeD
ID1 codeF
AS-Interface specificationV3.0
Auxiliary voltage (output)20 ... 30 V DC PELV
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Temperature influence0.0025 %/K of input signal range
ID code3
Degree of protectionEN 60529:2000
ConnectionRemovable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Mass110 g
Current loading capacity 100 mA from AS-Interface; overload and short-circuit resistant
600 mA From auxiliary voltage UAUX (AUX switch position) , overload and short-circuit protected
LED FAULTFault indication: red LED
Red: communication error or address is 0
Red flashing: peripheral fault
Accuracy0.1 % of input signal range at 25 В°C (298 K)
Rated operating current 70 mA (without sensors) / max. 200 mA
Climatic conditionsFor indoor use only
AS-InterfaceEN 62026-2:2013
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
Pollution degree2
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks

Buy Pepperl+Fuchs VBA-2E-KE5-IJL/UJL with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is a fast-developing company in the supply of industrial automation devices. We can offer millions of automation parts for any application. Your order can be delivered to any continent. Become our client and get exclusive prices for the entire range of products. A quick response is our main advantage. We are constantly growing to satisfy all your needs in electrical equipment supply.