  • A/B slave with extended addressing possibility for up to 62 slaves
  • Inputs for 3-wire sensors
  • Power supply of the inputs and outputs from the external auxiliary voltage
  • Connection of actuators and sensors via cable outputs with M8 connectors
  • Communication monitoring
  • Function display for bus, external auxiliary voltage, in- and outputs
  • Cable piercing method with gold plated contact pins
Item Number: VBA-3E3A-G20-ZEL/E2L-P1
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
Current loading capacity500 mA , overload and short-circuit protected
ID1 code7
Voltage (UAUX - 0.5 V)
AS-Interface specificationV3.0
Supplyfrom external auxiliary voltage UAUX
Supplyfrom external auxiliary voltage UAUX
ID2 codeE
LED OUTSwitching state (output); 3 LED yellow
Mass260 g
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
MTBF110 a
Data bits (function via AS-Interface) input output
Parameter bits (programmable via AS-i)function
IO code7
Required master specification V2.1
Storage temperature-25 ... 85 ?°C (-13 ... 185 ?°F)
Number/Type3 Inputs for 3-wire sensors (PNP), DC
Current2 A per output
TB 40 ?°C: 6 A total
TB 60 ?°C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A
ConnectionAS-Interface, AUX: Insulation piercing technology
Yellow flat cable/black flat cable
Inputs/outputs: M8 round plug connector in accordance with EN 61076-2-104
Inputs: LF004-GS1-A (4-pin, bushing contacts, screw lock, A-coded)
Matching connector: LM004-Gx1-A or similar
Outputs: NF003-SS1-A (3-pin, bushing contacts, snap lock, A-coded)
Matching connector: NM003-Sx1-A or similar
Fieldbus standardEN 62026-2:2013
Degree of protectionEN 60529:2000
Rated operating voltage26.5 ... 31.6 V from AS-Interface
NoteThe flat cable routing is designed for 100 actuation cycles
Signal delay< 1 ms (input/AS-Interface)
Mounting2 clips with andempty; 8 mm drill hole
InputEN 61131-2:2007
Switching pointaccording to DIN EN 61131-2
0 (undamped) 0.5 mA
1 (damped) 2.0 mA
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
AS-InterfaceEN 62026-2:2013
Degree of protectionIP54 according to EN 60529
Rated operating current 35 mA
Slave typeA/B slave
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
Auxiliary voltage (output)20 ... 30 V DC PELV
Number/Type3 electronic outputs, PNP, overload and short-circuit proof
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
Cable length1 m
Input current 8 mA (limited internally)
UL File NumberE223772 ""For use in NFPA 79 Applications only""
LED INswitching state (input); 3 LED yellow
ID codeA
Ambient temperature-25 ... 60 ?°C (-13 ... 140 ?°F)
ProfileS-7.A.E
Emitted interferenceEN 61000-6-4:2007

Buy Pepperl+Fuchs VBA-3E3A-G20-ZEL/E2L-P1 with the best possible price and delivery terms on eltra-trade.com

eltra-trade.com is an online store of industrial automation equipment. New items of automation products are added every day. Your order can be quickly delivered throughout Europe and around the world. We offer you good value for money. We provide our customers with a very quick response and good conditions. Using our professional services will help you be more competitive in the market and it will save you time.