Pepperl+Fuchs VBA-3E3A-G20-ZEL/E2L-P1
AS-Interface I/O module
We ship to United States of America!
- A/B slave with extended addressing possibility for up to 62 slaves
- Inputs for 3-wire sensors
- Power supply of the inputs and outputs from the external auxiliary voltage
- Connection of actuators and sensors via cable outputs with M8 connectors
- Communication monitoring
- Function display for bus, external auxiliary voltage, in- and outputs
- Cable piercing method with gold plated contact pins
Item Number:
VBA-3E3A-G20-ZEL/E2L-P1
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
Current loading capacity | 500 mA , overload and short-circuit protected |
ID1 code | 7 |
Voltage | (UAUX - 0.5 V) |
AS-Interface specification | V3.0 |
Supply | from external auxiliary voltage UAUX |
Supply | from external auxiliary voltage UAUX |
ID2 code | E |
LED OUT | Switching state (output); 3 LED yellow |
Mass | 260 g |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing |
MTBF | 110 a |
Data bits (function via AS-Interface) | |
Parameter bits (programmable via AS-i) | function |
IO code | 7 |
Required master specification | V2.1 |
Storage temperature | -25 ... 85 ?°C (-13 ... 185 ?°F) |
Number/Type | 3 Inputs for 3-wire sensors (PNP), DC |
Current | 2 A per output TB 40 ?°C: 6 A total TB 60 ?°C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A |
Connection | AS-Interface, AUX: Insulation piercing technology Yellow flat cable/black flat cable Inputs/outputs: M8 round plug connector in accordance with EN 61076-2-104 Inputs: LF004-GS1-A (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM004-Gx1-A or similar Outputs: NF003-SS1-A (3-pin, bushing contacts, snap lock, A-coded) Matching connector: NM003-Sx1-A or similar |
Fieldbus standard | EN 62026-2:2013 |
Degree of protection | EN 60529:2000 |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Note | The flat cable routing is designed for 100 actuation cycles |
Signal delay | < 1 ms (input/AS-Interface) |
Mounting | 2 clips with andempty; 8 mm drill hole |
Input | EN 61131-2:2007 |
Switching point | according to DIN EN 61131-2 0 (undamped) 0.5 mA 1 (damped) 2.0 mA |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
AS-Interface | EN 62026-2:2013 |
Degree of protection | IP54 according to EN 60529 |
Rated operating current | 35 mA |
Slave type | A/B slave |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Number/Type | 3 electronic outputs, PNP, overload and short-circuit proof |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
Cable length | 1 m |
Input current | 8 mA (limited internally) |
UL File Number | E223772 ""For use in NFPA 79 Applications only"" |
LED IN | switching state (input); 3 LED yellow |
ID code | A |
Ambient temperature | -25 ... 60 ?°C (-13 ... 140 ?°F) |
Profile | S-7.A.E |
Emitted interference | EN 61000-6-4:2007 |
Buy Pepperl+Fuchs VBA-3E3A-G20-ZEL/E2L-P1 with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com is an online store of industrial automation equipment. New items of automation products are added every day. Your order can be quickly delivered throughout Europe and around the world. We offer you good value for money. We provide our customers with a very quick response and good conditions. Using our professional services will help you be more competitive in the market and it will save you time.