Pepperl+Fuchs VBA-3E3A-G20-ZEL/E2L-P1
AS-Interface I/O module

Pepperl+Fuchs VBA-3E3A-G20-ZEL/E2L-P1
  • A/B slave with extended addressing possibility for up to 62 slaves
  • Inputs for 3-wire sensors
  • Power supply of the inputs and outputs from the external auxiliary voltage
  • Connection of actuators and sensors via cable outputs with M8 connectors
  • Communication monitoring
  • Function display for bus, external auxiliary voltage, in- and outputs
  • Cable piercing method with gold plated contact pins
Item Number: VBA-3E3A-G20-ZEL/E2L-P1
189.62
-
+
Total price: 189.62
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Current loading capacity500 mA , overload and short-circuit protected
ID1 code7
Voltage (UAUX - 0.5 V)
AS-Interface specificationV3.0
Supplyfrom external auxiliary voltage UAUX
Supplyfrom external auxiliary voltage UAUX
ID2 codeE
LED OUTSwitching state (output); 3 LED yellow
Mass260 g
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
MTBF110 a
Data bits (function via AS-Interface) input output
Parameter bits (programmable via AS-i)function
IO code7
Required master specification V2.1
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Number/Type3 Inputs for 3-wire sensors (PNP), DC
Current2 A per output
TB 40 В°C: 6 A total
TB 60 В°C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A
ConnectionAS-Interface, AUX: Insulation piercing technology
Yellow flat cable/black flat cable
Inputs/outputs: M8 round plug connector in accordance with EN 61076-2-104
Inputs: LF004-GS1-A (4-pin, bushing contacts, screw lock, A-coded)
Matching connector: LM004-Gx1-A or similar
Outputs: NF003-SS1-A (3-pin, bushing contacts, snap lock, A-coded)
Matching connector: NM003-Sx1-A or similar
Fieldbus standardEN 62026-2:2013
Degree of protectionEN 60529:2000
Rated operating voltage26.5 ... 31.6 V from AS-Interface
NoteThe flat cable routing is designed for 100 actuation cycles
Signal delay< 1 ms (input/AS-Interface)
Mounting2 clips with andempty; 8 mm drill hole
InputEN 61131-2:2007
Switching pointaccording to DIN EN 61131-2
0 (undamped) 0.5 mA
1 (damped) 2.0 mA
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
AS-InterfaceEN 62026-2:2013
Degree of protectionIP54 according to EN 60529
Rated operating current 35 mA
Slave typeA/B slave
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
Auxiliary voltage (output)20 ... 30 V DC PELV
Number/Type3 electronic outputs, PNP, overload and short-circuit proof
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
Cable length1 m
Input current 8 mA (limited internally)
UL File NumberE223772 ""For use in NFPA 79 Applications only""
LED INswitching state (input); 3 LED yellow
ID codeA
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
ProfileS-7.A.E
Emitted interferenceEN 61000-6-4:2007

Comments

No comments yet

Write a comment