Pepperl+Fuchs VBA-4E-G11-ZAJ-F
AS-Interface sensor module

Pepperl+Fuchs VBA-4E-G11-ZAJ-F
  • Inputs for 2-, 3-, and 4-wire sensors
  • Supply of sensors from AS-Interface
  • Function display for bus and inputs
  • Degree of protection IP68 / IP69K
  • Communication monitoring
  • Cable piercing method with gold plated contact pins
  • AS-Interface POWER24
Item Number: VBA-4E-G11-ZAJ-F
123.79
-
+
Total price: 123.79
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
InputEN 61131-2:2007
MountingMounting plate
Surge protectionUe: Over voltage category III, safe isolated power supplies (PELV)
ConnectionAS-Interface: AS-Interface flat cable
Inputs: M12 round connector
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: sensor supply overload
Mass200 g
Tightening torque, cable gland0.4 Nm
Altitude 2000 m above MSL
Emitted interferenceEN 61000-6-4:2007
Pollution degree3
Diagnostic Coverage (DC)0 %
Current loading capacity 200 mA, overload and short-circuit protected
ProfileS-0.A.2
Climatic conditionsFor indoor use only
ID1 code7
LED INswitching state (input); 4 LED yellow
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Slave typeA/B slave
ID2 code2
Parameter bits (programmable via AS-i)function
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Shock and impact resistance30 g, 11 ms in 6 spatial directions 3 shocks
10 g, 16 ms in 6 spatial directions 1000 shocks
ID codeA
Relative humidity85 % , noncondensing
Protection classIII
IO code0
AS-InterfaceEN 62026-2:2013
Degree of protectionEN 60529:2000
Data bits (function via AS-Interface) input output
Signal delay< 1 ms (input/AS-Interface)
UL File NumberE223772
Tightening torque, housing screws1.8 Nm
Rated operating current 40 mA (without sensors) / max. 240 mA
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Mission Time (TM)20 a
AS-Interface specificationV3.0
Degree of protectionIP68 / IP69K
Switching pointaccording to DIN EN 61131-2 (Type 2)
Input current 9 mA (limited internally)
Supplyfrom AS-Interface
Fieldbus standardEN 62026-2:2013
Required master specification V2.1
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
MTTFd120 a
Voltage12 ... 31 V
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
option 2 inputs for 4-wire sensors (PNP), DC
Rated operating voltage18,0 ... 31.6 V from AS-Interface

Comments

No comments yet

Write a comment