Pepperl+Fuchs VBA-4E-G4-Pt100
AS-Interface analog module
- Degree of protection IP65
- Flat or round cable connection (via standardized EMS base, not included with delivery)
- Cable piercing method for flat cable
- Function display for bus and inputs
Item Number:
VBA-4E-G4-Pt100
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Mass | 350 g |
Required master specification | V2.1 |
Degree of protection | IP65 |
Resolution | 16 Bit / 0.1 В°C |
IO code | 7 |
AS-Interface specification | V2.1 |
Degree of protection | EN 60529:2000 |
UL File Number | E223772 |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
LED ANALOG | status of input signal; LED green off: not connected (peripheral error) green: signal within measurement range green flashing: signal outside of measurement range (peripheral error) |
ID code | 3 |
Slave type | Standard slave |
Parameter bits (programmable via AS-i) | function |
Profile | S-7.3.E |
Mounting | DIN mounting rail |
LED FAULT | error display; LED red red: communication error red flashing: peripheral error |
Supply | from AS-Interface |
Connection | cable piercing method or terminal compartment yellow flat cable or standard round cable inputs: M12 x 1.5 cable gland and cage tension spring terminals |
MTTFd | 150 a at 30 В°C |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Protection class | III |
Number/Type | 4 inputs for Pt100, 2- or 3-wire connection |
Ambient temperature | 0 ... 70 В°C (32 ... 158 В°F) |
Rated operating current | 80 mA |
AS-Interface | EN 62026-2:2013 |
LED PWR | AS-Interface voltage; LED green |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
ID2 code | E |