Pepperl+Fuchs VBA-4E1A-KE3-ZEJ/SR
AS-Interface safety module

Pepperl+Fuchs VBA-4E1A-KE3-ZEJ/SR
  • Several safe output modules grouped to form a release circuit
  • 2 galvanically isolated contact banks
  • 4 conventional inputs, 1 of which can be switched as a protective feedback circuit
  • SIL3 (IEC 61508)
  • Addressing jack
  • Occupies one complete address for the safe output and one A/B address for the 4 inputs
Item Number: VBA-4E1A-KE3-ZEJ/SR
439.03
-
+
Total price: 439.03
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Sensor supply 90 mA
Signal frequency 250 Hz
Supplyfrom AS-Interface
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
ProfileS-7.A.E
Protection classIII
ID1 code5 (Can be changed to 7 or F)
ID2 codeE
Number/Type1 safety relay output
Required master specification V2.1
Auxiliary voltage (input)12 ... 30 V DC PELV
LED OUTFor flashing patterns see diagnostics table
AS-InterfaceEN 62026-2:2013
LED FAULTerror display; LED red
red: communication error
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Emitted interferenceEN 61000-6-4:2007
Ambient temperature0 ... 55 В°C (32 ... 131 В°F)
Voltage21 ... 31 V DC
Degree of protectionIP20
Slave typeA/B slave
LED INswitching state (input); 4 LED yellow
InputEN 61131-2
Supplyfrom AS-Interface
Current loading capacity 90 mA, overload- and short-circuit proof (INT)
LED ALARMPLC reports alarm; red LED
Parameter bits (programmable via AS-i)function
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
LED PWRAS-Interface voltage; LED green
AS-Interface specificationV2.1
Safety Integrity Level (SIL)SIL 3
Switching pointaccording to DIN EN 61131-2 (Type 2)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
UL File NumberE223772
Rated operating current 30 mA (without sensors) / max. 200 mA
Input current 8 mA (limited internally)
Surge protectionUEXT, Ue: Over voltage category III, safe isolated power supplies (PELV)
MountingDIN mounting rail
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Degree of protectionEN 60529:2000
Performance level (PL)PL e
Data bits (function via AS-Interface) input output
Usage categoryDC-13 and AC-15
ID codeA
IO code7
Signal delay< 2 ms (input/AS-Interface)

Comments

No comments yet