Pepperl+Fuchs VBA-4E2A-KE1-Z/E2
AS-Interface sensor/actuator module

Pepperl+Fuchs VBA-4E2A-KE1-Z/E2
  • A/B slave with extended addressing possibility for up to 62 slaves
  • Housing with removable terminals
  • Communication monitoring
  • Inputs for 2-wire sensors and mechanical contacts
  • Addressing jack
  • Power supply of outputs from the external auxiliary voltage
  • Power supply of inputs from the module
  • Function display for bus, ext. auxiliary voltage, inputs and outputs
Item Number: VBA-4E2A-KE1-Z/E2
163.44
-
+
Total price: 163.44
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Rated operating current 25 mA (without sensors) / max. 60 mA
InputEN 61131-2:2007
UL File NumberE87056
ID1 code7
Data bits (function via AS-Interface) input output
Mass80 g
Slave typeA/B slave
Usage categoryDC-13
CurrentO1/O2 max. 1.5 A, total 3 A (TB 40 В°C)
O1/O2 max. 1 A, total 2 A (TB 70 В°C)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Diagnostic Coverage (DC)0 %
ID codeA
Number/Type2 electronic outputs, PNP, overload and short-circuit proof
LED PWRAS-Interface voltage; LED green
Required master specification V2.1
Noise immunityEN 61000-6-2:2001
Emitted interferenceEN 61000-6-4:2001
Signal frequency 250 Hz
MTTFd270 a
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of outputs
IO code7
Supplyfrom external auxiliary voltage UAUX
LED INswitching state (input); 4 LED yellow
Number/Type4 inputs for 2-wire sensors (PNP), DC or for mechanical contacts
Relative humidity90 % , noncondensing
Auxiliary voltage (output)20 ... 30 V DC PELV
Input current 8 mA (limited internally)
ID2 code0
Pollution degree2
MountingDIN mounting rail
Voltage (UAUX - 0.5 V)
Switching pointaccording to DIN EN 61131-2 (Type 2)
LED OUTSwitching state (output); 2 LED yellow
Parameter bits (programmable via AS-i)function
Supplyfrom AS-Interface
Signal delay< 2 ms (input/AS-Interface)
AS-Interface specificationV2.1
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Mission Time (TM)20 a
ProfileS-7.A.0
LED AUXext. auxiliary voltage UAUX ; LED green
Protection classIII
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Degree of protectionIP20
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2

Comments

No comments yet

Write a comment