Pepperl+Fuchs VBA-4E3A-G20-ZEL/E2L-P11
AS-Interface I/O module
- A/B slave with extended addressing possibility for up to 62 slaves
- Inputs for 3-wire sensors
- Power supply of the inputs and outputs from the external auxiliary voltage
- Communication monitoring
- Function display for bus, external auxiliary voltage, in- and outputs
- Cable piercing method with gold plated contact pins
- M12 connection, e.g., suitable for Lenze Smart Motor drives and SEW MOVI-SWITCH
Item Number:
VBA-4E3A-G20-ZEL/E2L-P11
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Fieldbus standard | EN 62026-2:2013 |
Mounting | 2 clips with andempty; 8 mm drill hole |
Switching point | according to DIN EN 61131-2 0 (undamped) 0.5 mA 1 (damped) 2.0 mA |
LED IN | switching state (input); 4 LED yellow |
IO code | 7 |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
UL File Number | E223772 ""For use in NFPA 79 Applications only"" |
MTBF | 110 a |
LED OUT | Switching state (output); 3 LED yellow |
AS-Interface specification | V3.0 |
Degree of protection | EN 60529:2000 |
Input current | 8 mA (limited internally) |
Voltage | (UAUX - 0.5 V) |
AS-Interface | EN 62026-2:2013 |
Emitted interference | EN 61000-6-4:2007 |
Slave type | A/B slave |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Parameter bits (programmable via AS-i) | function |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing |
ID1 code | 7 |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Ambient temperature | -25 ... 60 В°C (-13 ... 140 В°F) |
Signal delay | < 1 ms (input/AS-Interface) |
ID2 code | E |
Current loading capacity | 500 mA , overload and short-circuit protected |
Number/Type | 4 Inputs for 3-wire sensors (PNP), DC |
Data bits (function via AS-Interface) | |
ID code | A |
Degree of protection | IP54 according to EN 60529 |
Number/Type | 3 electronic outputs, PNP, overload and short-circuit proof |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing |
Supply | from external auxiliary voltage UAUX |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Required master specification | V2.1 |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
Mass | 260 g |
Supply | from external auxiliary voltage UAUX |
Connection | AS-Interface, AUX: Insulation piercing technology Yellow flat cable/black flat cable Inputs/outputs: M12 round plug connector in accordance with EN 61076-2-101 Inputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar Outputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar |
Profile | S-7.A.E |
Note | The flat cable routing is designed for 100 actuation cycles |
Cable length | 0.7 m (Inputs) , 1.5 m (X1, X2) |
Input | EN 61131-2:2007 |
Current | 2 A per output TB 40 В°C: 6 A total TB 60 В°C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A |
Rated operating current | 35 mA |
People also buy
Comments
No comments yet