Pepperl+Fuchs VBA-4E3A-G20-ZEL/E2L-P5-KNAPP AS-Interface I/O module

Pepperl+Fuchs VBA-4E3A-G20-ZEL/E2L-P5-KNAPP
Item Number: VBA-4E3A-G20-ZEL/E2L-P5-KNAPP
  • A/B slave with extended addressing possibility for up to 62 slaves
  • Inputs for 3-wire sensors
  • Power supply of the inputs and outputs from the external auxiliary voltage
  • Communication monitoring
  • Function display for bus, external auxiliary voltage, in- and outputs
  • Cable piercing method with gold plated contact pins
  • M12 connection, e.g., suitable for Lenze Smart Motor drives and SEW MOVI-SWITCH
Price on Request
Quantity
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Auxiliary voltage (output)20 ... 30 V DC PELV
Current loading capacity500 mA , overload and short-circuit protected
NoteThe flat cable routing is designed for 100 actuation cycles
Supplyfrom external auxiliary voltage UAUX
Input current≤ 8 mA (limited internally)
Voltage≥ (UAUX - 0.5 V)
ID codeA
Switching pointaccording to DIN EN 61131-2
0 (undamped) ≤ 0.5 mA
1 (damped) ≥ 2.0 mA
LED OUTSwitching state (output); 3 LED yellow
Parameter bits (programmable via AS-i)function
Mass260 g
AS-Interface specificationV3.0
Mounting2 clips with ∅ 8 mm drill hole
InputEN 61131-2:2007
Cable length2 m
Fieldbus standardEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
ConnectionAS-Interface, AUX: Insulation piercing technology
Yellow flat cable/black flat cable
Inputs/outputs: M12 round plug connector in accordance with EN 61076-2-101
Inputs: LF type (4-pin, bushing contacts, screw lock, A-coded)
Matching connector: LM type or similar
Outputs: LF type (4-pin, bushing contacts, screw lock, A-coded)
Matching connector: LM type or similar
Supplyfrom external auxiliary voltage UAUX
Current2 A per output
TB ≤ 40 В°C: 6 A total
TB ≤ 60 В°C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
IO code7
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Signal delay< 1 ms (input/AS-Interface)
MTBF110 a
Rated operating current≤ 35 mA
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
Number/Type3 electronic outputs, PNP, overload and short-circuit proof
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Emitted interferenceEN 61000-6-4:2007
Number/Type4 Inputs for 3-wire sensors (PNP), DC
UL File NumberE223772 ""For use in NFPA 79 Applications only""
ProfileS-7.A.E
Data bits (function via AS-Interface) input output
LED INswitching state (input); 4 LED yellow
ID1 code7
Required master specification≥ V2.1
Slave typeA/B slave
Degree of protectionEN 60529:2000
Degree of protectionIP54 according to EN 60529
ID2 codeE

Comments

No comments yet

Write a comment