Pepperl+Fuchs VBA-4E3A-KE-ZE/R
AS-Interface sensor/actuator module

Pepperl+Fuchs VBA-4E3A-KE-ZE/R
  • A/B slave with extended addressing possibility for up to 62 slaves
  • Housing with removable terminals
  • Communication monitoring
  • Inputs for 2- and 3-wire sensors
  • Isolated relay output
  • Addressing jack
  • Supply of inputs external or from the module, as required
  • Function display for bus, internal input supply, inputs and outputs
Item Number: VBA-4E3A-KE-ZE/R
189.01
-
+
Total price: 189.01
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
AS-InterfaceEN 62026-2:2013
InputEN 61131-2:2004
Slave typeA/B slave
UL File NumberE106378
Input/AS-Interfacenone
Rated operating current 35 mA (without sensors) / max. 235 mA
Short-circuit-proofContact: 500 A / 40 ms
Current loading capacity 150 mA, overload- and short-circuit protected (INT)
Relative humidity85 % , noncondensing
Switching pointaccording to DIN EN 61131-2 (Type 2)
Input/OutputIN1 ... IN4 to O1 ... O3: safe isolation acc. to EN 60947-1,
rated insulation voltage 278 V AC
Signal delay< 2 ms (input/AS-Interface)
LED INswitching state (input); 4 LED yellow
Parameter bits (programmable via AS-i)function
Climatic conditionsFor indoor use only
Required master specification V2.1
Mass170 g
Switching off power500 VA
MTTFd330 a
Galvanic isolationEN 60947-1
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Altitude 2000 m above MSL
LED OUTSwitching state (output); 3 LED yellow
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
IO code7
Output/OutputO1 to O2, O3: safe isolation according to EN 60947-1,
rated insulation voltage 278 V AC
O2 to O3: basic insulation according to EN 60947-1,
rated insulation voltage 278 V AC
AS-Interface specificationV2.1
Auxiliary voltage (input)12 ... 30 V DC PELV
Pollution degree2
Usage categoryDC-13 and AC-14
ID codeA
Output/AS-Interfacesafe isolation acc. to EN 60947-1,
rated insulation voltage 278 V AC
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Degree of protectionIP20
Usage categoryEN 60947-5-1
LED INTInternal input supply active; LED green
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Pollution degreeEN 60947-5-1
Signal frequency 250 Hz
Noise immunityEN 61000-6-2:2005
Number/Type3 relay outputs, normally open
Emitted interferenceEN 61000-6-4:2007
ID2 code0
Surge protectionO1 ... O3: Over voltage category II
UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV)
Supplynone
Degree of protectionEN 60529:2000
Data bits (function via AS-Interface) input output
Switching delay< 10 ms (AS-Interface/contact)
Input current 8 mA (limited internally)
Diagnostic Coverage (DC)0 %
ID1 code7
Switching frequency< 20 Hz (without load)
< 0.1 Hz (nominal load)
Electromagnetic compatibilityNAMUR NE 21: 1998-08
Mission Time (TM)20 a
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
ProfileS-7.A.0
LED PWRAS-Interface voltage; LED green
Voltage21 ... 31 V DC (INT)
LED FAULTFault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
Tightening torque of clamping screws0.5 Nm ... 0.6 Nm
MountingDIN mounting rail

Comments

No comments yet

Write a comment