Pepperl+Fuchs VBA-4E4A-G2-ZA/EA2
AS-Interface sensor/actuator module

Pepperl+Fuchs VBA-4E4A-G2-ZA/EA2
  • AS-Interface certificate
  • Degree of protection IP67
  • Addressing jack
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Communication monitoring
  • Inputs for 2-, 3-, and 4-wire sensors
  • Power supply of outputs from the external auxiliary voltage
  • Supply for inputs from AS-Interface
  • Ground connection (FE) possible
  • Function display for bus, ext. auxiliary voltage, inputs and outputs
  • Detection of overload on sensor supply
  • Detection of output overload
Item Number: VBA-4E4A-G2-ZA/EA2
266.50
-
+
Total price: 266.50
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Current0.5 A per output , 2 A total
ID2 code7
LED PWRAS-Interface voltage; LED green
Climatic conditionsFor indoor use only
Noise immunityEN 61000-6-2:2001
Data bits (function via AS-Interface) input output
InputEN 61131-2:2007
IO code7
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
ID1 code7
AS-InterfaceEN 62026-2:2013
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Degree of protectionIP67
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Relative humidity85 % , noncondensing
Degree of protectionEN 60529:2000
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Tightening torque, cable gland0.4 Nm
Mass150 g
UL File NumberE223772
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Diagnostic Coverage (DC)0 %
Parameter bits (programmable via AS-i)function
ProfileS-7.A.7
Voltage21 ... 31 V
Pollution degree3
Altitude 2000 m above MSL
Voltage (UAUX - 0.5 V)
AS-Interface specificationV3.0
Emitted interferenceEN 61000-6-4:2001
ID codeA
Signal delay< 2 ms (input/AS-Interface)
Slave typeA/B slave
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating current 40 mA (without sensors) / max. 220 mA
LED OUTSwitching state (output); 4 LED yellow
Supplyfrom AS-Interface
Signal frequency 250 Hz
Fieldbus standardEN 62026-2:2013
Mission Time (TM)20 a
Input current 9 mA (limited internally)
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
option 2 inputs for 4-wire sensors (PNP), DC
MountingMounting plate
Required master specification V3.0
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or outputs
MTTFd140 a
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
LED INswitching state (input); 4 LED yellow
Current loading capacity 180 mA (TB 40 В°C),
140 mA (TB 60 В°C), , overload and short-circuit protected
Protection classIII
Switching pointaccording to DIN EN 61131-2 (Type 2)
LED AUXext. auxiliary voltage UAUX ; LED green

Comments

No comments yet