Pepperl+Fuchs VBA-4E4A-KE-ZE/R
AS-Interface sensor/actuator module
- Housing with removable, mechanical and color coded terminals
- Communication monitoring
- Inputs for 2- and 3-wire sensors
- Isolated relay output
- Addressing jack
- Selectable supply to the sensors: External or from the module
- Function display for bus, internal sensor supply, inputs, and outputs
Item Number:
VBA-4E4A-KE-ZE/R
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
LED INT | Internal input supply active; LED green |
Input current | 8 mA (limited internally) |
Data bits (function via AS-Interface) | |
Auxiliary voltage (input) | 12 ... 30 V DC PELV |
Parameter bits (programmable via AS-i) | function |
AS-Interface | EN 62026-2:2013 |
ID2 code | 7 |
Tightening torque of clamping screws | 0.5 Nm ... 0.6 Nm |
LED IN | switching state (input); 4 LED yellow |
Control circuit | 8 mA per relay (from AS-Interface) |
Input/AS-Interface | Switch position INT: None Switch position EXT: reinforced insulation, rated insulation voltage 66 V DC |
Ambient temperature | -25 ... 60 В°C (-13 ... 140 В°F) |
Emitted interference | EN 61000-6-4:2007 |
Input | EN 61131-2:2004 |
Degree of protection | IP20 |
Switching point | according to DIN EN 61131-2 (Type 2) |
IO code | 7 |
Degree of protection | EN 60529:2000 |
AS-Interface specification | V3.0 |
Profile | S-7.A.7 |
Mounting | DIN mounting rail |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
UL File Number | E106378 |
Galvanic isolation | EN 60947-1:2007 |
Fieldbus standard | EN 62026-2:2013 |
MTTFd | 300 a |
Current loading capacity | 150 mA, overload- and short-circuit protected (INT) |
Relative humidity | 85 % , noncondensing |
Mission Time (TM) | 20 a |
Pollution degree | 2 |
Usage category | DC-13 and AC-14 |
Required master specification | V3.0 |
Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) |
Rated operating current | 35 mA (no sensors)/max. 210 mA |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Number/Type | 4 relay outputs, normally open |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
Output/Output | basic insulation, rated insulation voltage 300 V AC |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
LED OUT | Switching state (output); 4 LED yellow |
Mass | 170 g |
Diagnostic Coverage (DC) | 0 % |
LED PWR | AS-Interface voltage; LED green |
Slave type | A/B slave |
Climatic conditions | For indoor use only |
ID code | A |
Altitude | 2000 m above MSL |
Voltage | 21 ... 31 V DC (INT) |
Surge protection | O1 ... O4: Over voltage category II UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV) |
Supply | none |
Signal delay | < 2 ms (input/AS-Interface) |
Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 |
LED FAULT | Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply |
Output/AS-Interface | safe isolation, rated insulation voltage 300 V AC |
Switching delay | < 10 ms (AS-Interface/contact) |
Input/Output | safe isolation, rated insulation voltage 300 V AC |
ID1 code | 7 |
People also buy