Pepperl+Fuchs VBA-4E4A-KE5-ZEJQ/R
AS-Interface sensor/actuator module

Pepperl+Fuchs VBA-4E4A-KE5-ZEJQ/R
We ship to United States of America!
  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Selectable supply to the sensors: External or from the module
  • Function display for bus, internal sensor supply, inputs, and outputs
Item Number: VBA-4E4A-KE5-ZEJQ/R
178.54
-
+
Total price: 178.54
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Current loading capacity 150 mA, overload- and short-circuit protected (INT)
Control circuit 11 mA per relay (from AS-Interface)
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Output/AS-Interfacesafe isolation, Rated insulation voltage 252 Veff
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Altitude 2000 m above MSL
Surge protectionO1 ... O4: Over voltage category II
UEXT, Ue: overvoltage category II, safe isolated power supplies (PELV)
Data bits (function via AS-Interface) input output
Slave typeA/B slave
LED INTInternal input supply active; LED green
IO code7
Output/OutputBasic insulation, rated insulation voltage 250 Veff, in phase
Number/Type4 inputs for 3-wire sensors (PNP), DC
ID codeA
Usage categoryDC-13 and AC-14
Climatic conditionsFor indoor use only
LED OUTSwitching state (output); 4 LED yellow
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Supplynone
Switching delay< 10 ms (AS-Interface/contact)
Relative humidity85 % , noncondensing
Electrical safetyIEC 61140:2009
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED FAULTFault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
Emitted interferenceEN 61000-6-4:2007
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Pollution degree2
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Auxiliary voltage (input)12 ... 30 V DC PELV
Number/Type4 relay outputs, normally open
Degree of protectionIP20
Installation in an enclosure with a minimum protection class of IP54 required
Galvanic isolationEN 60664-1:2007
Input/Outputsafe isolation, Rated insulation voltage 252 Veff
UL File NumberE223772
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Input current 5.6 mA (max.)
Input/AS-InterfaceSwitch position INT: None Switch setting EXT: safe isolation, rated insulation voltage 92 Veff
Required master specification V3.0
Mass125 g
Signal delay< 1 ms (input/AS-Interface)
Voltage21 ... 31 V DC (INT)
InputEN 61131-2:2004
ID1 code7
MTBF224 a
LED INswitching state (input); 4 LED yellow
Fieldbus standardEN 62026-2:2013
Switching pointaccording to DIN EN 61131-2 (type 1)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Rated operating current 35 mA (without sensors) / max. 230 mA
MountingDIN mounting rail
ProfileS-7.A.7
AS-Interface specificationV3.0
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
ConnectionRemovable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Parameter bits (programmable via AS-i)function
ID2 code7

Buy Pepperl+Fuchs VBA-4E4A-KE5-ZEJQ/R with the best possible price and delivery terms on eltra-trade.com

eltra-trade.com is your go-to source for industrial electrical parts. Our extensive product range includes various automation equipment, available for fast worldwide delivery. We guarantee high quality and competitive pricing. Make us your trusted partner for all your electrical supply needs.

Comments

No comments yet

Write a comment