Pepperl+Fuchs VBG-PB-K20-D-EV24
AS-Interface gateway
- Connection to PROFIBUS DP
- Easy commissioning and fault diagnosis via LEDs and graphic display
- PROFIBUS DP V1 support
- Dublicate addressing detection
- Earth fault detection
- AS-Interface noise detection
- AS-Interface POWER24
Item Number:
VBG-PB-K20-D-EV24
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Ambient temperature | 0 ... 55 В°C (32 ... 131 В°F) |
LED CONFIG ERR | configuration error; LED red |
PROFIBUS | Sub-D interface |
AS-Interface specification | V3.0 |
EMC monitoring | integrated |
Switch SET | Selection and setting of a slave address |
LED PRG ENABLE | autom. programming; LED green |
Duplicate address detection | from AS-Interface slaves |
Degree of protection | EN 60529:2000 |
Button MODE | Mode selection PRJ-operation/save configuration/cursor |
Display | Illuminated graphical LC display for addressing and error messages |
UL approval | An isolated source with a secondary open circuit voltage of 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
AS-Interface | spring terminals, removable |
AS-Interface | EN 62026-2:2013 |
OK button | Mode selection traditional-graphical/confirmation |
LED AS-i ACTIVE | AS-Interface operation normal; LED green |
Construction type | Low profile housing , Stainless steel |
MTTFd | 105 a at 30 В°C |
Diagnostics function | Extended function via display |
Interface type | Chip card slot |
Power supply | max. 4 A per AS-Interface circuit |
UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
Protocol | PROFIBUS DP V1 |
LED POWER | voltage ON; LED green |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
ESC button | Mode selection traditional-graphical/cancel |
Insulation voltage | 500 V |
Electromagnetic compatibility | EN 61326:2003 |
Rated operating current | approx. 250 mA |
LED U AS-i | AS-Interface voltage; LED green |
Earth fault detection | integrated |
LED PROFIBUS | PROFIBUS communication active; LED green |
Mass | 500 g |
LED PRJ MODE | projecting mode active; LED yellow |
Interface type | RS-485 |
Degree of protection | IP20 |
Transfer rate | 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection |
PLC-Functionality | activateable |
Rated operating voltage | 24 V DC ( 20 ... 31.6 V ) safe isolated power supplies (PELV) Note 24 V power supply, max. segment length: 50 m Supply via AS-Interface power supply, max. segment length: 100 m |
People also buy
Comments
No comments yet