Pepperl+Fuchs VBG-PB-K30-DMD-S16-EV
AS-Interface Gateway/Safety Monitor

Pepperl+Fuchs VBG-PB-K30-DMD-S16-EV
  • Gateway and safety monitor in one housing
  • Connection to PROFIBUS DP
  • SafeLink
  • Certified up to SIL 3 according to IEC 61508 and EN 62061 and up to PLe according to EN 13849
  • 2 AS-Interface networks
  • 2 safe output relays and 2 safe electronic outputs
  • Integrated data decoupling
  • Diagnostics via RJ45 Ethernet port
Item Number: VBG-PB-K30-DMD-S16-EV
2657.29
-
+
Total price: 2657.29
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Construction typeLow profile housing , Stainless steel
Rated operating current 300 mA off AS interface network 1
70 mA off AS interface network 2
Interface typeRS-485
ProtocolPROFIBUS DP V1
Diagnostics functionExtended function via display
Switch-on delay< 10 s
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-6-4:2007
LED AS-i ACTIVEAS-Interface operation normal; LED green
Button4
AS-Interface specificationV3.0
LED CONFIG ERRconfiguration error; LED red
UL File NumberE223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Earth fault detectionintegrated
LED U AS-iAS-Interface voltage; LED green
Transfer rate9.6 kBit/s / 12 MBit/s , Automatic baud rate detection
Ambient temperature0 ... 55 В°C (32 ... 131 В°F)
LED output circuitOutput circuit closed; 4 x green LEDs
Performance level (PL)PL e
EMC monitoringintegrated
LED EDM/StartExternal device monitoring circuit inputs closed, 4x yellow LEDs
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Number/Type4 EDM/Start inputs:
EDM: Inputs for the external device monitoring circuits
Start: start inputs:
Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 andmu;s)
Response delay< 40 ms
AS-Interfacespring terminals, removable
Safety outputOutput circuits 1 and 2: 2 potential-free contacts,
max. contact load:
3 ADC-13 at 30 VDC,
3 AAC-15 at 30 VAC
Output circuits 3 and 4: 2 PNP transistor outputs
max. contact load:
0.5 ADC-13 at 30 VDC
Degree of protectionIP20
Rated operating voltage26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC
B10d2 E+7
PROFIBUSSub-D interface
Degree of protectionEN 60529:2000
LED AUXext. auxiliary voltage UAUX ; LED green
StandardsIEC 61508:2010 (SIL3) IEC 62061:2005 (SIL3) EN ISO 13849-1:2008 (PL e)
MTTFd200 a
UL approvalAn isolated source with a secondary open circuit voltage of 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed.
UL mark does not provide UL certification for any functional safety rating or aspects of the device.
PLC-Functionalityactivateable
LED PRG ENABLEautom. programming; LED green
Fieldbus standardPROFIBUS according to DIN 19245 Part 3
Safety Integrity Level (SIL)SIL 3
LED PROFIBUSPROFIBUS master detected; LED green
LED PRJ MODEprojecting mode active; LED yellow
AS-InterfaceEN 62026-2:2013
Interface typeEthernet: RJ-45
Diagnostic Interface
Insulation voltage 500 V
DisplayIlluminated graphical LC display for addressing and error messages
LED POWERvoltage ON; LED green
Interface typeChip card slot
Mass800 g
Duplicate address detectionfrom AS-Interface slaves

Comments

No comments yet

Write a comment