Supplyloop power for field devices
voltage 8 ... 23 V DC, adjustable in steps of 0.1 V

Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Dimensions92 x 89.5 x 92.8 mm (without cable glands and antenna)
EU-Type Examination CertificateBVS 17 ATEX E 029
Parameter assignment- wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP)
- device variables mapping
- publishing of up to ten burst messages in a wireless network, period and trigger mode selectable
- notification of up to five events from adapter and/or connected device(s) in a wireless network
- scaling and linearization of 4 ... 20 mA signal of connected analog device
- tuning of supply parameters for the connected device
- locking/unlocking of device parameterization
Rated voltage7.2 V DC , battery operated
Degree of protectionIP66
Accuracycurrent input: 0.125 % of measuring range
Suitable field devicesusable for:
- one point-to-point connection with a HART field device, or
- one point-to-point connection with a 4 ... 20 mA field device, or
- up to four externally powered HART field devices operating in multidrop mode
Ambient temperature-40 ... 60 В°C (-40 ... 140 В°F)
Massapprox. 750 g
Connectionterminals 1, 2, 3, 4, 5, 6
multiple wirings available , depending on operating mode
Output variablesPV: loop current
SV, TV, QV:configurable according to user requirement
- adapter: temperature, battery voltage, energy consumed and estimated battery life-time
- 4 ... 20 mA device: scaled or linearized process value
- HART device: up to four process variables
Radio and telecommunication terminal equipmentThe usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
Output rated operating current4 ... 20 mA
Vibration resistance20 ... 2000 Hz, 0,01 g2/Hz
Current4 ... 20 mA
Materialplastic
Influence of ambient temperaturecurrent input: 5 µA/K
Mountingmounting on field device , panel or pole mounting
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
test setup and execution acc. to EN 60068-2-60
Designationbattery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately)
mounting set W-ACC-F8MK
threads (NPT 1/2"", NPT 3/4"", G 1/2, M20)
Degree of protectionIEC 60529

Comments