Poles description | 3P |
Protected poles description | 3t |
Network type | AC |
Network frequency | 50/60 Hz |
[In] rated current | 80 A ( 65 В°C ) |

Item Number:
28105
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Datasheet
- Alternative numbers
- Comments
Poles description | 3P |
Protected poles description | 3t |
Network type | AC |
Network frequency | 50/60 Hz |
[In] rated current | 80 A ( 65 В°C ) |
[Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Circuit breaker rating code | H |
Breaking capacity | Icu 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 Icu 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Icu 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 Icu 25 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 Icu 6 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 65 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 10 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 |
[Ics] rated service breaking capacity | Ics 6 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2 Ics 25 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 Ics 25 kA 525 V AC 50/60 Hz conforming to IEC 60947-2 Ics 65 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 70 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics 100 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Utilisation category | Category A |