Sick PAC50-BGB
Pressure sensors
- Electronic pressure switch for pneumatic applications
- Large display shows system pressure, output states and set switching points
- Three large function keys and intuitive menu navigation
Item Number:
PAC50-BGB
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Specification:
Part Number | 1062959 |
Storage temperature: | -20 °C ... +80 °C |
Gauge pressure: | -1 bar ... 0 bar; -1 bar ... +1 bar; 0 bar ... +6 bar; 0 bar ... +10 bar |
Rated temperature range: | +10 °C ... +60 °C |
Ambient temperature: | 0 °C ... +60 °C |
CRUus certificate: | + |
Zero point adjustment: | Max. + 5 % of span |
Non-repeatability: | ≤ ± 0.2 % of span |
RoHS certificate: | + |
Setting accuracy of switching outputs: | ≤ ± 0.2 % of span |
Process connection: | 2 x G ? |
Enclosure rating: | IP 65 / IP 67 According to IEC 60529 |
Relative humidity: | ≤ 90 % |
Non-linearity: | ≤ ± 0.5 % (of span (Best Fit Straight Line, BFSL) according to IEC 61298-2) |
Vibration load: | Max. 5 g (10 ... 150 Hz), xyz, according to DIN EN 60068-2-6 |
CULus certificate: | - |
Power consumption: | Max. 40 mA at L+ = 24 VDC |
CE-conformity: | EMC directive: 2004/108/EC, EN 61326-2-3 |
Process temperature: | 0 °C ... +60 °C |
Measuring range: | -1 bar ... 1 bar |
Weight sensor: | Ca. 40 g |
Output signal: | PNP/NPN/Push-Pull + 4 mA ... 20 mA / 0 V … 10 V |
Pressure type: | Gauge pressure |
Shock load: | Max. 30 g, xyz according to IEC 60068-2-27 (11 ms, mechanical shock) |
Electrical safety: | Short-circuit protection: QA, Q1, Q2 towards M and L+, Protection class: III, Overvoltage protection: 32 V DC, Reverse polarity protection: L+ towards M |
Protection class III: | + |
Medium: | Dry compressed air |
Housing material: | Seals: NBR, Housing: polycarbonate, DIN rail mounting: POM, Buttons: TPE |
Analog signal output and ohmic load RA: | Load resistance for voltage output > 3 kOhm, Load resistance for current output < 600 Ohm, Optional, 4 mA ... 20 mA / 0 V… 10 V. Automatic detection depending on connected load or programmable. Output signals can be inverted: 20 mA … 4 mA / 10 V … 0 V |
Initialization time: | 300 ms |
Display: | Update: 1,000, 500, 200, 100 ms (adjustable), Pressure display: 4 digits, 16 segments, Pressure unit in display can be switched: bar, MPa, kPa, psi and inHg, LCD with LED backlight (green/red), can be rotated electronically by 180° |
Accuracy: | ≤ ± 1.5 % of span (Including non-linearity, hysteresis, zero point and full scale error (corresponds to error of measurement according to IEC 61298-2)), ≤ ± 2 % of span incl. temperature error (Including non-linearity, hysteresis, zero point and full scale error (corresponds to error of measurement according to IEC 61298-2)) |
People also buy
Comments
No comments yet