Sick PAC50-DND
Pressure sensor

Sick PAC50-DND
We ship to United States of America!
PAC50-DND PRESSURE SWITCH art. 1083734
Item Number: PAC50-DND
238.24
-
+
Total price: 238.24
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Sick PAC50-DND

Datasheet:

  • Article: 1083734
  • Media: Dry compressed air
  • Pressure type: Relative pressure
  • Pressure unit: bar
  • Measuring range: 0 bar ... 10 bar
  • Overload protection: 15 bar
  • Operating temperature: 0 °C ... +60 °C
  • li>Analogue output signal and load capacity RA: Optional, 4-20 mA / 0-10 V. Automatic switching depending on the connected load or hard tuning. Invertible output signals: 20-4 mA / 10-0 V, Load resistance for current output < 600 ?, Load resistance for voltage output > 3 k?,
  • Zero point correction: Max. + 5% interval
  • Output signal: IO-Link/PNP + PNP/NPN/Push-Pull
  • Diagnostic output: Digital output 2 can be used as diagnostic output
  • Display: LCD display with LED backlight (color green/red), electronic, 180° rotatable, Pressure display: 4 digits, 16 segments, Unit of measurement switchable on the indicator: bar, MPa, kPa, psi and inHg, Update: 1000, 500, 200, 100 ms (programmable),
  • Initialization time: 300 ms
  • Technical connections: ј" NPT female
  • Housing material: Housing: polycarbonate, Pushbuttons: TPE, DIN rail mounting: POM, Seals: NBR
  • Connection type: Circular connector M12 x 1, 4-pin
  • Supply voltage: 17– 30 V DC
  • Current consumption: Max 40 mA at L+ = 24 V DC
  • Electrical safety: Protection class: III, Overvoltage protection: 32 In DC, Short circuit resistance: QA, Q1, Q2 relative to M and L+, Polarity inversion protection: L+ relative to M,
  • EC compliance: EU Electromagnetic Compatibility Directive: 2004/108/EC, EN 61326-2-3
  • Sensor weight: Approx. 40 g
  • Protection type: IP65 / IP67 (according to IEC 60529)
  • Protection class III: ?
  • RoHS certificate: ?
  • cRUus Certificate: ?
  • Non-linearity: ? ± 0.5% span (Best Fit Straight Line, BFSL) according to IEC 61298-2
  • Accuracy: ? ± 1.5% span
  • Setting accuracy of discrete outputs: ? ± 0.2% of span
  • Repeatability of measurement results: ? ± 0.2% of span
  • Range of nominal temperatures: +10 °C ... +60 °C
  • Ambient temperature: 0 °C ... +60 °C
  • Storage temperature: –20 °C ... +80 ° C
  • Relative humidity: ? 90%
  • Shock resistance: Max. 30 g, xyz, according to DIN EN 60068-2-27 (11 ms, mechanical shock)
  • Vibration resistance: Max. 5 g (10–150 Hz), xyz, according to DIN EN 60068-2-6
  • Pressure unit: bar
  • Category: Pressure sensors
  • Series: PAC50
  • Media: dry compressed air
  • Pressure type: relative pressure

Buy Sick PAC50-DND with the best possible price and delivery terms on eltra-trade.com

eltra-trade.com provides top-notch industrial control components. Our online catalog features a diverse selection of products, all available for fast delivery. Benefit from our competitive prices and excellent customer support. Trust us to meet your automation equipment requirements efficiently.

Comments

No comments yet

Write a comment