Pepperl+Fuchs ICE1-8DI8DO-G60L-C1-V1D Fieldbus module

Pepperl+Fuchs ICE1-8DI8DO-G60L-C1-V1D
Item Number: ICE1-8DI8DO-G60L-C1-V1D
  • Multiprotocol-compatible
  • Decentralized control function
  • M12 power connector
  • Sturdy metallic housing
  • Web-based configuration
438.28
Quantity
-
+
Total price: 438.28
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments
Interface typeIndustrial Ethernet
Relative humiditymax. 95 %
Physical M12, D-coded
Tightening torque, fastening screws1 Nm
UL File NumberE223772
Tightening torque of clamping screws0.5 Nm
Cold start temperature-40 В°C (-40 В°F)
Current consumption120 mA
Noise immunityEN 61000-6-2:2005
LED indicationsee manual
Mass500 g
Pollution degree3
Shock and impact resistance50 g, 11 ms, all axes
Current loading capacitymax. 16 A per module (for UL applications, max. 9 A)
Vibration resistance15 g at 5 - 500 Hz
Nominal voltage24 V DC
Output rated operating currentmax. 2 A per channel (X5 – X8) / 4 A Per port
Storage temperature-40 ... 70 В°C (-40 ... 158 В°F)
Galvanic isolationbetween US and UL
Sensor supplymax. 200 mA Per port (X1 – X4)
Contact elementsPA
Degree of protectionIP65/IP67/IP69K
Number/Type8 digital inputs (X1 – X4), 8 digital outputs (X5 – X8)
Inputs: 2-, 3-, 4-wire PNP, DC, supply from US
Outputs: 2-, 3-, 4-wire, PNP, DC, supply from UL
Short-circuit protected
Altitude0 ... 2000 m
Rated operating voltage18 ... 30 V
Degree of protectionEN 60529:2000
ProtocolPROFINET IO with media redundancy protocol (MRP)
EtherNet/IP with Device Level Ring (DLR)
EtherCAT
Rotary switchSetting the fieldbus protocol
ConnectionPower Supply M12, L-coded
Fieldbus M12, D-coded
Inputs/Outputs M12, A-coded
Nominal current16 A
Tightening torque, cable glandmax. 0.5 Nm
Ambient temperature-20 ... 70 В°C (-4 ... 158 В°F)
Emitted interferenceEN 61000-6-4:2007+A1:2011
Construction typeField housing
Transfer rate10/100 Mbps

Comments

No comments yet

Write a comment