Pepperl+Fuchs NBN4-12GM50-E2-Y292473 Inductive sensor


Item Number: NBN4-12GM50-E2-Y292473
- 4 mm non-flush
- Overview
- Datasheet
- Alternative numbers
- Comments
Operating current | 0 ... 200 mA |
Connection assembly | AMP housing 282105-1 AMP crimp 282404-1 AMP sealing 281934-2 Schlemmer corrugated tube 1926304 Cable bushing: MTA 45.20921 |
Scope of delivery | 2 self locking nuts in scope of delivery |
Output polarity | DC |
Voltage drop | 3 V |
MTTFd | 990 a |
Reduction factor r304 | 0.8 |
Diagnostic Coverage (DC) | 0 % |
Core cross-section | 0.34 mm2 |
Switching frequency | 0 ... 1200 Hz |
Reduction factor rCu | 0.4 |
Output type | 3-wire |
Repeat accuracy | 0.01 mm |
UL approval | cULus Listed, General Purpose |
Rated operating distance | 4 mm |
Housing diameter | 12 mm |
CCC approval | CCC approval / marking not required for products rated 36 V |
Housing material | brass, nickel-plated |
Assured operating distance | 0 ... 3.24 mm |
Mission Time (TM) | 20 a |
Degree of protection | IP67 |
Ambient temperature | -25 ... 70 В°C (-13 ... 158 В°F) |
Connection type | cable PVC , L1 = 395 mm , L2 = 280 mm |
Hysteresis | typ. 5% |
Short-circuit protection | pulsing |
No-load supply current | 17 mA |
Switching state indicator | LED, yellow |
Reduction factor rAl | 0.5 |
Installation | non-flush |
Sensing face | PBT |
Reverse polarity protection | reverse polarity protected |
Off-state current | 0 ... 0.5 mA typ. 0.1 andmicro;A at 25 В°C |
Operating voltage | 10 ... 30 V |
People also buy
Comments
No comments yet