Pepperl+Fuchs NJ15-30GK-SN-15M Inductive sensor


Item Number: NJ15-30GK-SN-15M
- 15 mm non-flush
- Usable up to SIL 3 acc. to IEC 61508
- ATEX approval Ex-i and Ex-nA/tc for zone 0-2 and zone 20-22
- Degree of protection IP68
- Overview
- Datasheet
- Alternative numbers
- Comments
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 80 В°C (176 В°F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 61 В°C (141.8 В°F) |
Housing material | Crastin (PBTB), black |
Switching function | Normally closed (NC) |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
EAC conformity | TR CU 012/2011 |
Type of protection | intrinsic safety |
Type of protection | intrinsic safety |
Degree of protection | IP68 |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW , T6 : 73 В°C (163.4 В°F) T5 : 88 В°C (190.4 В°F) T4 : 100 В°C (212 В°F) T3 : 100 В°C (212 В°F) T2 : 100 В°C (212 В°F) T1 : 100 В°C (212 В°F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW , T6 : 69 В°C (156.2 В°F) T5 : 84 В°C (183.2 В°F) T4 : 100 В°C (212 В°F) T3 : 100 В°C (212 В°F) T2 : 100 В°C (212 В°F) T1 : 100 В°C (212 В°F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW , T6 : 51 В°C (123.8 В°F) T5 : 66 В°C (150.8 В°F) T4 : 80 В°C (176 В°F) T3 : 80 В°C (176 В°F) T2 : 80 В°C (176 В°F) T1 : 80 В°C (176 В°F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW , T6 : 39 В°C (102.2 В°F) T5 : 54 В°C (129.2 В°F) T4 : 61 В°C (141.8 В°F) T3 : 61 В°C (141.8 В°F) T2 : 61 В°C (141.8 В°F) T1 : 61 В°C (141.8 В°F) |
Reduction factor r304 | 0.85 |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Effective internal inductance | max. 180 andmicro;H A cable length of 10 m is considered. |
Connection type | cable silicone , 15 m |
CCC approval | CCC approval / marking not required for products rated 36 V |
Type of protection | intrinsic safety |
Effective internal inductance | max. 180 andmicro;H A cable length of 10 m is considered. |
Mission Time (TM) | 20 a |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. : using an amplifier in accordance with EN 60947-5-6 : 58 В°C (136.4 В°F) at UBmax = 9 V , RV = 562 andOmega; : 58 В°C (136.4 В°F) |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
Diagnostic Coverage (DC) | 0 % |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. using an amplifier in accordance with EN 60947-5-6 : 58 В°C (136.4 В°F) at UBmax = 9 V , RV = 562 andOmega; : 58 В°C (136.4 В°F) |
Assured operating distance | 0 ... 12.15 mm |
Possible characteristics | maximum operating voltage UBmax , maximum load current ILmax , minimum series resistance RV , maximum analog output voltage UAmax , maximum analog output current IAmax |
Rated operating distance | 15 mm |
Equipment protection level | Ga , Gb , Gc (ic) , Gc (nA) , Da , Dc , Mb |
Type of protection | intrinsic safety |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 В°C (212 В°F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 В°C (212 В°F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 80 В°C (176 В°F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 61 В°C (141.8 В°F) |
CE marking | [*PD-Z02585A*] |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 20 V , Ii = 25 mA , Pi = 34 mW , T6 : 55 В°C (131 В°F) T5 : 55 В°C (131 В°F) T4 : 55 В°C (131 В°F) T3 : 55 В°C (131 В°F) T2 : 55 В°C (131 В°F) T1 : 55 В°C (131 В°F) at Ui = 20 V , Ii = 25 mA , Pi = 64 mW , T6 : 55 В°C (131 В°F) T5 : 55 В°C (131 В°F) T4 : 55 В°C (131 В°F) T3 : 55 В°C (131 В°F) T2 : 55 В°C (131 В°F) T1 : 55 В°C (131 В°F) at Ui = 20 V , Ii = 52 mA , Pi = 169 mW , T6 : 41 В°C (105.8 В°F) T5 : 41 В°C (105.8 В°F) T4 : 41 В°C (105.8 В°F) T3 : 41 В°C (105.8 В°F) T2 : 41 В°C (105.8 В°F) T1 : 41 В°C (105.8 В°F) at Ui = 20 V , Ii = 76 mA , Pi = 242 mW , T6 : 29 В°C (84.2 В°F) T5 : 29 В°C (84.2 В°F) T4 : 29 В°C (84.2 В°F) T3 : 29 В°C (84.2 В°F) T2 : 29 В°C (84.2 В°F) T1 : 29 В°C (84.2 В°F) |
Output type | NAMUR with safety function |
Nominal voltage | 8.2 V |
Effective internal inductance | max. 180 andmicro;H A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. |
Output type | 2-wire |
CE marking | [*PD-Z02585A*] |
Reduction factor rCu | 0.3 |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
CE marking | [*PD-Z02585A*] |
CE marking | [*PD-Z02586A*] |
Sensing face | Crastin (PBTB), black |
Core cross-section | 0.75 mm2 |
CE marking | [*PD-Z02586A*] |
Installation | non-flush |
Ambient temperature | -40 ... 100 В°C (-40 ... 212 В°F) |
Switching frequency | 0 ... 100 Hz |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
UL approval | cULus Listed, General Purpose |
Possible characteristics | maximum operating voltage UBmax , maximum load current ILmax , minimum series resistance RV , maximum analog output voltage UAmax , maximum analog output current IAmax |
Effective internal inductance | max. 180 andmicro;H A cable length of 10 m is considered. |
Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the ""exida Functional Safety Assessment"" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. |
Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
Safety Integrity Level (SIL) | SIL 3 |
Use in the hazardous area | see instruction manuals |
Reduction factor rAl | 0.4 |
MTTFd | 11850 a |
Effective internal inductance | max. 180 andmicro;H A cable length of 10 m is considered. |
Type of protection | ""n"" |
Type of protection | Protection by enclosure ""tc"" |
People also buy
Comments