Pepperl+Fuchs NJ2-11-N-G-910 Inductive sensor

Pepperl+Fuchs NJ2-11-N-G-910
Item Number: NJ2-11-N-G-910
  • Comfort series
91.70
Quantity
-
+
Total price: 91.70
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments
Effective internal inductancemax. 50 µH ; a cable length of 10 m is considered.
Installationflush
Nominal voltage8 V
Diagnostic Coverage (DC)0 %
Switching frequency0 ... 3000 Hz
Output typeNAMUR
Appropriate typeNJ 2-11-N-G...
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
Actual operating distance1.8 ... 2.2 mm
Effective internal capacitancemax. 30 nF ; a cable length of 10 m is considered.
Connection typecable PVC , 2 m
Assured operating distance0 ... 1.62 mm
ATEX marking II 1D Ex ia IIIC T135В°C Da
The Ex-related marking can also be printed on the enclosed label.
Degree of protectionIP68
Output type2-wire
UL approvalcULus Listed, General Purpose
Sensing facePVDF
CE marking[*PD-Z02585A*]
Switching functionNormally closed (NC)
Core cross-section0.34 mm2
Housing materialnickel-plated steel
Appropriate typeNJ 2-11-N-G...
Reduction factor rAl 0.4
Reduction factor r304 0.85
Use in the hazardous areasee instruction manuals
Hysteresis0.5 ... 3.5 typ. 2 %
ATEX marking II 2G Ex ia IIC T6…T1 Gb
The Ex-related marking can also be printed on the enclosed label.
Ambient temperature-25 ... 100 В°C (-13 ... 212 В°F)
Effective internal inductancemax. 50 µH
A cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Reduction factor rCu 0.3
Mission Time (TM)20 a
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
CE marking[*PD-Z02585A*]
MTTFd5887 a
Effective internal capacitancemax. 30 µF
A cable length of 10 m is considered.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection ""Intrinsic safety""
Use is restricted to the following stated conditions
Rated operating distance2 mm

Comments

No comments yet

Write a comment