Pepperl+Fuchs FB2212BR

Digital Output with Position Feedback
Pepperl+Fuchs FB2212BR
421.26
One click request
Dimensions28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
Switching point/switching hysteresis1.2 ... 2.1 mA / В± 0.2 mA
Vibration resistanceEN 60068-2-6
Shock resistanceEN 60068-2-27
EAC approvalRussia: RU C-IT.MIII06.B.00129
Line fault detectioncan be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms)
Number of channels2
Internal resistor1 kandOmega;
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Internal resistor329 andOmega;
Minimum pulse duration1 ms
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
EU-Type Examination CertificatePTB 97 ATEX 1074 U
Power dissipation1.3 W
Current limit53 mA
Line fault detectioncan be switched on/off for each channel via configuration tool
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Electromagnetic compatibilityNE 21
Damaging gasEN 60068-2-42
Occupied slots1
Rated voltage12 V DC , only in connection with the power supplies FB92**
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Codingoptional mechanical coding via front socket
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Connectionchannel I: 2+, 5-; channel II: 3+, 6-
Connectionchannel I: 1+, 4-
LED indicationLED green: supply
LED red: output line fault
LED yellow: status output
Response time20 ms (depending on bus cycle time)
ATEX approvalPTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U
Massapprox. 350 g
Connectionbackplane bus
Number of channels1
Connectionbackplane bus
System informationThe module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Relative humidity95 % non-condensing
Open loop voltage25.3 V
Degree of protectionIEC 60529
Interfacemanufacturer-specific bus to standard com unit
Power consumption1.8 W
Relative humidityEN 60068-2-56
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Environmental testEN 60068-2-14
in international format without spaces
All fields are required