Pepperl+Fuchs FB2213BR

Digital Output with Position Feedback
Pepperl+Fuchs FB2213BR
433.76
One click request
Power dissipation1.5 W
Response time20 ms (depending on bus cycle time)
System informationThe module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Line fault detectioncan be switched on/off for each channel via configuration tool
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
EAC approvalRussia: RU C-IT.MIII06.B.00129
Connectionchannel I: 2+, 5-; channel II: 3+, 6-
Open loop voltage26.7 V
Degree of protectionIEC 60529
Relative humidityEN 60068-2-56
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Damaging gasEN 60068-2-42
Shock resistanceEN 60068-2-27
Internal resistor1 kandOmega;
Line fault detectioncan be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms)
Number of channels2
Number of channels1
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 350 g
Internal resistor509 andOmega;
Vibration resistanceEN 60068-2-6
Switching point/switching hysteresis1.2 ... 2.1 mA / В± 0.2 mA
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Occupied slots1
Current limit40 mA
LED indicationLED green: supply
LED red: output line fault
LED yellow: status output
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
EU-Type Examination CertificatePTB 97 ATEX 1074 U
Rated voltage12 V DC , only in connection with the power supplies FB92**
Connectionbackplane bus
Codingoptional mechanical coding via front socket
Dimensions28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Power consumption1.5 W
Minimum pulse duration1 ms
Interfacemanufacturer-specific bus to standard com unit
Relative humidity95 % non-condensing
Environmental testEN 60068-2-14
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Connectionchannel I: 1+, 4-
ATEX approvalPTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U
Electromagnetic compatibilityNE 21
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Connectionbackplane bus
in international format without spaces