Pepperl+Fuchs FB2217E3 Digital Output with Position Feedback

Pepperl+Fuchs FB2217E3
Item Number: FB2217E3
  • 1-channel
  • 1 digital output, 2 digital inputs
  • Inputs and output Ex ia
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Line fault detection switched on and off
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown input
522.90
Quantity
-
+
Total price: 522.90
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments
Line fault detectioncan be switched on/off for each channel via configuration tool
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Degree of protectionIEC 60529
EU-type examination certificatePresafe 19 ATEX 14054U
Relative humidity95 % non-condensing
Massapprox. 750 g
Connectionbackplane bus / booster terminals
IECEx approvalIECEx PRE 19.0009U
Connectionchannel I: 2+, 5-; channel II: 3+, 6-
Line fault detectioncan be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms)
System informationThe module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Number of channels2
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Connectionbackplane bus
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (O: output, I1: input 1, I2: input 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1)
Connectionchannel I: 1+, 4-
Rated voltageUse only in connection with the power supplies FB92**
Current limit50 mA
Codingoptional mechanical coding via front socket
Internal resistor131 Ω
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Relative humidityEN 60068-2-56
Interfacemanufacturer-specific bus to standard com unit
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Number of channels1
Occupied slots1
Shock resistanceEN 60068-2-27
Dimensions28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
Environmental testEN 60068-2-14
Vibration resistanceEN 60068-2-6
Open loop voltage16.5 V
Damaging gasEN 60068-2-42
Internal resistor1 kΩ
Response time10 ms (depending on bus cycle time)
ATEX approvalPresafe 19 ATEX 14054U
Switching point/switching hysteresis1.2 ... 2.1 mA / В± 0.2 mA
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Power consumption1.85 W
Power dissipation1.3 W
Minimum pulse duration1 ms
Electromagnetic compatibilityNE 21

Comments

No comments yet

Write a comment