Pepperl+Fuchs HiCTB16-TRI-DOISS-EL-PL-Y1 Termination Board


Item Number: HiCTB16-TRI-DOISS-EL-PL-Y1
- System board for Triconex (approval TAN48)
- For 16-channel DO cards 3604E and 3624
- For 16 modules
- Recommended modules: HiC2873 (DO), HiC2877 (DO)
- 24 V DC supply
- Hazardous area: pluggable screw terminals, blue
- Safe area: ELCO socket, 56-pin
- Overview
- Datasheet
- Alternative numbers
- Comments
IECEx approval | IECEx CES 06.0003 |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered |
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. |
Mass | approx. 840 g |
Power dissipation | ≤ 500 mW , without modules |
Degree of protection | IP20 |
Storage temperature | -40 ... 70 В°C (-40 ... 158 В°F) |
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers |
Material | housing: polycarbonate, 30 % glass fiber reinforced |
EC-Type Examination Certificate | CESI 06 ATEX 022 |
Fusing | 4 A , in each case for 16 modules |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin |
Dimensions | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly |
Ripple | ≤ 10 % |
Electromagnetic compatibility | NE 21:2011 For further information see system description. |
Degree of protection | IEC 60529:2001 |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Reverse polarity protection | yes |