Pepperl+Fuchs KCD2-SOT-2.SP

Switch Amplifier
Pepperl+Fuchs KCD2-SOT-2.SP
173.24
One click request
Connection sidecontrol side
Connectionterminals 5, 6; 7, 8
Degree of protectionIP20
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Signal typeDigital Input
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Rated current50 mA
Labelingspace for labeling at the front
Protection against electrical shockIEC 61010-1:2010
Power dissipation≤ 800 mW including maximum power dissipation in the output
Connection sidefield side
Configurationvia DIP switches
Ripple≤ 10 %
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Rated voltage30 V DC
Rated voltage19 ... 30 V DC
Output IIsignal ; Transistor
ConnectionPower Rail or terminals 9+, 10-
Switching frequency≤ 5 kHz
Dimensions12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Response time≤ 200 µs
Display elementsLEDs
Output Isignal ; Transistor
Control elementsDIP-switch
Electromagnetic compatibilityNE 21:2011
InputEN 60947-5-6:2000
Signal level1-signal: (external voltage) - 3 V max. for 50 mA
0-signal: blocked output (off-state current ≤ 10 µA)
Output/power supplybasic insulation according to EN 50178, rated insulation voltage 50 Veff
Degree of protectionIEC 60529:2001
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Connectionspring terminals
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Connectionterminals 1+, 2-; 3+, 4-
Pulse/Pause ratiomin. 100 µs / min. 100 µs
Output/Outputbasic insulation according to EN 50178, rated insulation voltage 50 Veff
Massapprox. 100 g
Rated current30 ... 20 mA
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-GY(-UPR-03)
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Collective error messagePower Rail
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Safety Integrity Level (SIL)SIL 2
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
in international format without spaces